To use this function, it is necessary to have at least firmware version 4.30 on the REG-DIN-8 and to use a RegConfig version 4.30 or later.
This logic was created with the aim to manage the speed of more than 8 fan coils in different rooms independently with a 0/10V.
Foreword
The REG System provides up to 8 Dehumidifier/Integration units, therefore, if in a system there are up to 8 fan coils, in as many rooms it is possible, for each zone, to manage a fan coil, using the Dehumidifiers page used as Integration, independently. For example, if there are 4 zones each with a fan coil for heating and cooling (or only cooling), each zone will be associated with a Dehumidifier in the Integration column:
PHOTO TBD
In the Dehumidifier page, on each sub page D1, D2, D3, and D4 will be set:
Integration control “Active if requested” in summer and winter (if the room is to be both heated or cooled)
Valve control “Active if requested” if the Circuit is associated in the Dehumidifier page, if it is associated in the Zone page the Valve control may be left off
“Associated circuit” if managed from the Dehumidifiers page
The values in % of the low, medium, and high speeds of the Integration flow rates
PHOTO TBD
Low, medium, or high speed of each fan coil depends on the integration offset set in Configuration 2:
PHOTO TBD
Therefore, if the difference between the temperature read by the sensor of each zone and the set point set exceeds 1 K, the fan coil speed will be low, if it exceeds 2 K it will be medium and if it exceeds 3 K it will be high.
In the REGDIN OUTPUT page, the Analog Outputs to be connected to the 4 fan coils are the speeds of each dehumidifier (used as Integration) independent of each other:
PHOTO TBD
If the fan coils are more than 8, it is no longer possible to follow this path.
In questo caso la zona determina la propria velocità (alta/media/bassa) sempre facendo riferimento ai valori di offset in Configurazione 2 (come nel caso appena illustrato); questa valutazione è fatta da ogni zona in maniera autonoma e indipendente facendo la differenza tra il valore della temperatura letta dal sensore associato alla zona e il set point ambiente.
In seguito ogni zona “prende in prestito” dall’Integratore a cui è collegata (che in questo caso non svolge una vera funzione, ma “presta” semplicemente delle impostazioni) il valore dell’uscita 0/10V che corrisponde alla velocità che ha già determinato.
Questo valore viene trasmesso sull’uscita 0/10 associata ad ogni zona (nel caso in cui alla zona non sia associato un Integratore, lo 0/10 della zona trasmette il relativo set point ambiente).
Management > 8 fan coils by 0/10V
In this case, the zone determines its own speed (high/medium/low) always referring to the offset values in Configuration / 2 (as in the case just illustrated): this evaluation is made by each zone autonomously and independently by making the difference between the value of the temperature read by the sensor associated with the zone and the room set point.
Then, each zone “borrows” from the Integrator to which it is connected (which in this case does not perform a proper function, but it simply “lends” settings) the value of the 0/10V output that corresponds to the speed it has already determined.
This value is transmitted on the 0/10 output associated with each zone (if the zone is not associated with an Integrator, the 0/10 of the zone transmits the relative room set point).
1. Definizione degli offset di Integrazione in Configurazione 2
Come nel caso con meno di 8 fan coil è necessario definire gli offset di integrazione in Configurazione 2. Si ipotizzi di utilizzare gli stessi offset dell’esempio precedente.
Definition of Integration offset in Configuration 2
As in the case with less than 8 fan coils, it is necessary to define integration offset in Configuration 2. Assume to use the same offset as in the previous example.
2. Definizione delle stanze e dei gruppi di velocità di fan coil
Si ipotizzi di avere 10 stanze ognuna delle quali viene riscaldata e raffrescata da 1 fan coil, che vengono associati alla zona nella colonna Integrazione:
Definition of room and fan coil speed groups
Assume having 10 rooms, each of which is heated and cooled by 1 fan coil, which are associated with the zone in the Integration column:
PHOTO TBD
Il Sistema REG può gestire al massimo 8 gruppi di velocità di fan coil, visto che 8 sono le unità di Deumidificazione/Integrazione disponibili a cui appoggiarsi, quindi nel caso in esame è necessario individuare due coppie di stanze in cui ragionevolmente si possono gestire con le stesse velocità fan coil che non si trovano nello stesso ambiente, nell’esempio si definisce:
Soggiorno e Ingresso → Integrazione 1 (1 fan coil per ciascuna zona)
Cucina → Integrazione 2 (1 fan coil)
Camera 1 → Integrazione 3 (1 fan coil)
Camera 2 → Integrazione 4 (1 fan coil)
Camera 3 → Integrazione 5 (1 fan coil)
Sala da Pranzo → Integrazione 6 (1 fan coil)
Bagno 1 e Bagno 2 → Integrazione 7 (1 fan coil per ciascun bagno)
Studio → Integrazione 8 (1 fan coil)
The REG System can manage maximum 8 fan coil speed groups, as 8 are the available Dehumidifier/Integration units to rely on, therefore in the case at hand it is necessary to identify two pairs of room in which, reasonably, it is possible to manage with the same speed fan coils which are not in the same room, in the example are defined:
Living Room and Hall → Integration 1 (1 fan coil for each zone)
Kitchen → Integration 2 (1 fan coil)
Room 1 → Integration 3 (1 fan coil)
Room 2 → Integration 4 (1 fan coil)
Room 3 → Integration 5 (1 fan coil)
Dining Room → Integration 6 (1 fan coil)
Bathroom 1 e Bathroom 2 → Integration 7 (1 fan coil for each bathroom)
Study → Integration 8 (1 fan coil)
Note
In questo esempio non è previsto che unità di deumidificazione/integrazione possano essere utilizzate per altro (ad esempio una VMC). Ma nel caso in cui le unità di deumidifica e integra disponibili fossero meno di 8 è necessario unificare il più possibile i fan coil che hanno la stessa mappatura tra velocità e volt. Quindi se si ipotizza che due unità di deumidifica/integra siano già impegnate i 10 fan coil dell’esempio potrebbero essere raggruppati come segue:
Soggiorno e Ingresso → Integrazione 1 (1 fan coil per ciascuna zona)
Cucina → Integrazione 2 (1 fan coil)
Camera 1 / 2 / 3 → Integrazione 3 (1 fan coil per ogni camera)
Bagno 1 e Bagno 2 → Integrazione 4 (1 fan coil per ciascun bagno)
Sala da pranzo → Integrazione 5 (1 fan coil)
Studio → Integrazione 6 (1 fan coil)
è infatti ragionevole ipotizzare che stanze con la stessa destinazione d’uso possano condividere la stessa mappatura di velocità dei fan coil.
In this example it is not provided which dehumidifier/integration units can be used for anything else (e.g., a VMC). But, if the available dehumidification/integration unit are less than 8, it is necessary to unify as much as possible the fan coil that have the same mapping between speed and volts. Therefore, if it is assumed that two dehumidification/integration units are already occupied, the 10 fan coils in the example could be grouped as follows:
Living Room and Hall → Integration 1 (1 fan coil for each zone)
Kitchen → Integration 2 (1 fan coil)
Room 1 / 2 / 3 → Integration 3 (1 fan coil for each zone)
Bathroom 1 e Bathroom 2 → Integration 4 (1 fan coil for each zone)
Dining Room → Integration 5 (1 fan coil)
Study → Integration 6 (1 fan coil)
It is reasonable to assume that rooms with the same intended use can share the same fan coil speed mapping.
3. Impostazione dei gruppi di velocità dei fan coil
Nel gruppo di velocità di fan coil che fanno capo al deumidificatore 1 nella pagina Deumidificatori D1 è necessario impostare solamente:
le Portate d’aria dell’Integrazione in % da 0 a 100 in bassa, media e alta velocità
PHOTO TBD
Le portate d’aria possono essere tutte diverse in base alle esigenze del singolo gruppo di velocità di fan coil. Ad esempio nella camera 1 le portate sono più basse rispetto al gruppo Soggiorno/Ingresso:
PHOTO TBD
Se due zone si appoggiano alla stessa unità di Integrazione per prendere il valore 0/10 di velocità non è detto che la velocità a cui vengono gestiti i fan coil sia la stessa.
Prendiamo ad esempio la zona Soggiorno e Ingresso dall’immagine al punto 2 si nota che:
la temperatura letta dal sensore in Soggiorno è 28,9°C con set point 27°C → delta = 1,9 K
la temperatura letta dalla sonda nell’Ingresso è 30°C con set point 25,5°C → delta = 4,5 K
quindi il fan coil del Soggiorno andrà a velocità bassa (4 V - 40%) perché il delta è compreso tra 2 (offset di media velocità) > 1,9 K > 1 K (offset di bassa velocità), mentre il fan coil dell’ingresso andrà a velocità alta (9 V - 90%) perché il delta è 4,5 K > 3 K (offset di alta velocità).
4. Assegnare le uscite 0/10V
Nella pagina Uscite REGDIN le Uscite Analogiche da collegare ai 10 fan coil non sono più le velocità di ciascun deumidificatore (utilizzato come Integrazione), ma il valore 0/10 trasmesso da ogni singola zona, che corrisponde al valore 0/10 della velocità (alta/media/bassa definita dalla zona) presa dall’unità di integrazione associata alla zona stessa:
PHOTO TBD
Quindi nella pagina Uscite REGDIN si associa ad esempio:
UA1/0: set point zona 1 (Soggiorno) da collegare all’ingresso 0/10V del fan coil del Soggiorno
UA2/0: set point zona 2 (Cucina) da collegare all’ingresso 0/10V del fan coil della Cucina
UA1/1: set point zona 3 (Camera 1) da collegare all’ingresso 0/10V del fan coil della Camera 1
UA2/1: set point zona 4 (Camera 2) da collegare all’ingresso 0/10V del fan coil della Camera 2
Un impianto di questo tipo necessita di molte uscite 0/10V (tante quante sono i fan coil installati), quindi si consiglia di utilizzare i moduli REG-IOC, che hanno 2 uscite analogiche 0/10V ciascuno e possono essere impostati nella pagina Uscite IO/B dal numero 92 a 99:
PHOTO TBD
Attenzione
Attualmente anche se viene mostrato il valore NC (Non Configurato) le funzione è comunque attiva, per verificare il voltaggio in uscita è necessario utilizzare un tester.
Si allega il preset dell’esempio riportato:
Infine se in una stanza è presente più di un fan coil, è sufficiente ripetere quanto illustrato fino a qui, semplicemente bisogna associare a più uscite analogiche (in base a quanti fan coil ci sono) il valore 0/10 della zona/stanza che ha più fan coil.
Ad esempio se la zona 10 (Studio) avesse 2 fan coil la pagina Uscite IO/B dedicherebbe 2 uscite analogiche alla zona 10:
PHOTO TBD
E' evidente che in questo caso essendo il sensore ambiente lo stesso, le uscite UA2/94 e UA1/95 avranno sempre lo stesso valore e i due fan coil lavoreranno alla stessa velocità.