Determining the Working Mode of a Zone
The first step is to choose in which Working Mode you want the zone to work in, which can be:
Comfort: the zone is active and maintains ideal comfort condition: the controlled device is switched on or off to maintain the “Comfort” temperature (follows the Comfort set point); a zone is typically in Comfort mode during the hours it is in use.
Economy: the zone is active in diminished mode to save energy: the controlled device is switched on or off to maintain the “Economy” temperature (follows the Economy set point); a zone is typically in Economy mode during the hours when it is not being actively used, although it is not completely switched off.
Off/Antifreeze: the zone is off, the controlled device (pump, valve, etc.) is switched off, regardless of the detected temperature; in this working mode the zone is activated only if frost conditions are detected (see ANTIFREEZE MODE).
The current Working mode of a zone is determined:
By the Global enable status of the system: if the system is globally off, the Zones are in OFF, regardless of other factors (exceptions to this rule the Zones with special work mode in DHW, see USE A ZONE AS DHW SUBSYSTEM);
By the Zone Enable signal (which is set in the Configuration Zone/1 sub page), if defined and not active, it will take the Zone in OFF mode (see ANALOG AND DIGITAL INPUT MULTIPLEXER);
By the Global Season status of the system: if the system is in summer and the zone is programmed to work only in winter, it will be off regardless of other factors. The season in which the zone can work can be chosen in the Season column in the Configuration Zone/1 sub page and can be: never, summer, winter, or summer+winter.
Here are some examples:
Bathrooms in heat+cool systems: normally, in summer mode bathrooms are disabled; the corresponding zone will be configured to be active only in winter.
Towel heaters of the bathrooms; the corresponding zone will be configured to be active only in winter.
In a mixed system, radiant floor to heat + fan coil to cool, the zones controlling the floor will be active only in winter, the zones controlling the fan-coils will be active only in summer.
PHOTO TBD
By the Timetable with which the zone is associated, that can have up to 8 time slots set (Comfort, Economy, Off/Antifreeze), see TIMETABLES, or the zone can always be set to Comfort, Economy, OFF, without using the timetables.
By the possible Working mode that can be only Comfort, Economy, Comfort+Economy, or Never, and it is chosen from the Mode column in the Configuration Zone/1 sub page. In fact, a zone can be configured to work only when the associated timetable is in a specific working mode (Comfort or Economy). For example: bathroom towel heaters can be configured to work only when the corresponding timetable is in comfort mode.
PHOTO TBD
By the Force Working Mode, that is a parameter that is able to force the Working Mode of the Zone, bypassing all the determination logic listed in the previous steps.
PHOTO TBD
The Force Working Mode can be: Force Comfort, Force Economy, Force Antifreeze, or Automatic (meaning that it goes with what you have selected on the Timetable column) and it is chosen from the Zone Parameters sub page.
Here are some examples:
Let's assume you have a zone in Comfort Mode associated with a timetable which is in the Economy time slot: the zone will be therefore Off, because the only possible way to work is Comfort if in automatic. If you forced the zone in Economy, then it would be turn on in Economy.
Let's assume you have a zone in Comfort+Economy Mode associated with a Timetable that is in OFF in that time, also the zone will be consequently in OFF.
Note
The Force Working Mode of the Zone parameter has priority over the timetable itself and over its forcing. For this reason, if the Zone is forced into a certain mode, the working mode given by the associated timetable will be ignored. This is because in certain situation a single clock is associated with several zones (think of the day zone and night zone timetable). However, if a room needs to be switched off or on in Comfort, for example, by forcing it the associated timetable can be bypassed without “disturbing” the operation of the other zones associated with the same timetable.
Forcing the working mode bypasses the logic of determining the status of a zone and the Working Mode will be manually set by the user.
At the end of this process, the final Working Mode is determined, whose main function is to determine the Setpoint for the next step.
The current working mode is shown in the Status column on the left side of the Zone page.
Il Parametro di Forzatura del Modo di Lavoro della Zona è prioritario rispetto all'orologio stesso ed alla sua forzatura; per questo motivo, nel caso la Zona sia forzata in un certo modo, verrà ignorato il modo di lavoro dato dall'orologio associato. Questo perchè in alcune situazioni un solo orologio è associato a più zone (si pensi all’orologio zona giorno e zona notte). Se però una stanza necessità di essere spenta o accesa in Comfort, ad esempio, forzandola si può bypassare l’orologio associato senza “disturbare” il funzionamento delle altre zone associate allo stesso orologio.
Forzare il modo di Lavoro bypassa la logica di determinazione dello stato di una zona e il Modo di Lavoro verrà impostato manualmente dall'utente.
Alla fine di questo processo si viene quindi a determinare il Modo di Lavoro definitivo della Zona, la cui funzione principale è quella di determinare il Setpoint per la fase successiva.
Il modo di lavoro corrente della zona si vede nella colonna Stato a sinistra nella pagina Zone.
Attenzione
Nella sottopagina Configurazione Zona/1 c'è una colonna Forzatura, che non ha nulla a che vedere con la Forzatura del Modo di Lavoro, vedere MANUAL OVERRIDE).
Determinazione dell'Attivazione di una Zona
Una volta determinato il Modo di Lavoro, e con esso il Setpoint di Zona (vedere ZONE SET POINT AND SENSOR SETTING), si passa alla fase di determinazione dello stato di Attivazione della zona.
In questa fase viene confrontata la lettura di temperatura del sensore di zona con il setpoint, e, tenendo conto della Stagione Corrente dell'impianto e del Modo di Lavoro (Economy, Comfort o Antigelo), viene deciso se attivare o disattivare la zona:
Stagione Impostata: Il sistema in primo luogo valuta la stagione in cui ci si trova poi procede allo step successivo.
Modo di Lavoro: Una volta stabilita la stagione attuale, il sistema verifica il modo di lavoro attuale (Comfort, Economy o Spento), stabilito in base a quanto definito al paragrafo precedente.
Temperatura ambiente: Una volta determinato il set corrente, il Sistema REG tiene monitorato il valore di Temperatura rilevato dal sensore e agisce sull'output di zona per controllare la temperatura.
Naturalmente l'attivazione/disattivazione dell'output varia in funzione della stagione:
Se il sistema è in Inverno, l'output viene attivato se la temperatura rilevata è inferiore rispetto al set di temperatura e disattivato se la temperatura sale nuovamente al di sopra del set impostato (+ l’isteresi)
Se il sistema è in Estate, l'output viene attivato se la temperatura rilevata è superiore rispetto al set di temperatura e disattivato se la temperatura scende nuovamente al di sotto del set impostato (- l’isteresi)
Se la zona è Attiva l’Output della zona è spuntato, altrimenti è bianco:
L’output può essere utilizzato per attivare valvole termostatiche, fan coil, valvole a 2 vie ecc. in base alla funzione della zona.
USCITE DIGITALI DISPONIBILI
Per ogni zona è disponibile una sola uscita Digitale:
16. Zona 1 - Output della zona 1
17. Zona 2 - Output della zona 2
ecc. fino alla zona 32 che corrisponde all’uscita gigitale 47.
USCITE ANALOGICHE DISPONIBILI
Per ogni zona è disponibile una sola uscita analogica:
21. Setpoint Zona 1 - set point corrente della zona 1
22. Setpoint Zona 2 - set point corrente della zona 1
ecc. fino alla zona 32 che corrisponde all’uscita analogica 52.
Attenzione
Se alla zona è associato un Deumidificatore per l’Integrazione nella sottopagina Configurazione Zona/1:
Allora fare riferimento a EN_GESTIONE > 8 FAN COIL CON 0/10V.