The ambient compensation allows you to increase or decrease the water temperature (whether climate curve or direct set point controlled) based on the error present between the desired ambient set point and the measured ambient temperature.
...
On the Circuits page, within the Circuit you want to activate the Ambient compensation on, you must enter a non-zero value in “Positive Ambient Compensation Limit” and in “Negative Ambient Compensation Limit”:PHOTO TBD
...
If these two parameters are zero, the ambient compensation will not be accomplished.
In the considered case, the set point is 28°C30°C, the positive Compensation (the maximum possible increase on the set point) is 10 K, the desired temperature is 33°C35°C, which is the set point + the correction that comes from the zone (5 K).
...
In heating mode, a positive compensation increases the set point, in cooling mode it is lowered
In heating mode a negative compensation lowers the set point, in cooling it is increased
...
Warning
If a compensation ambient circuit is activated, it is possible that also the dew point management will use the same circuit to attempt to increase the water outlet temperature. The circuit associated with the zone in Configuration Zone / 1 will not be used if present.