To use this function, it is necessary to have at least firmware version 4.30 on the REG-DIN-8 and to use a RegConfig version 4.30 or later.

...

The REG System provides up to 8 Dehumidifier/Integration units, therefore, if in a system there are up to 8 fan coils, in as many rooms it is possible, for each zone, to manage a fan coil, using the Dehumidifiers page used as Integration, independently. For example, if there are 4 zones each with a fan coil for heating and cooling (or only cooling), each zone will be associated with a Dehumidifier in the Integration column:

PHOTO TBD

In the Dehumidifier page, on each sub page D1, D2, D3, and D4 will be set:

  • Integration control “Active if requested” in summer and winter (if the room is to be both heated or cooled)

  • Valve control “Active if requested” if the Circuit is associated in the Dehumidifier page, if it is associated in the Zone page the Valve control may be left off

  • “Associated circuit” if managed from the Dehumidifiers page

  • The values in % of the low, medium, and high speeds of the Integration flow rates

PHOTO TBD

Low, medium, or high speed of each fan coil depends on the integration offset set in Configuration 2:

PHOTO TBD

Therefore, if the difference between the temperature read by the sensor of each zone and the set point set exceeds 1 K, the fan coil speed will be low, if it exceeds 2 K it will be medium and if it exceeds 3 K it will be high.

In the REGDIN OUTPUT page, the Analog Outputs to be connected to the 4 fan coils are the speeds of each dehumidifier (used as Integration) independent of each other:

PHOTO TBD

If the fan coils are more than 8, it is no longer possible to follow this path.

In questo caso la zona determina la propria velocità (alta/media/bassa) sempre facendo riferimento ai valori di offset in Configurazione 2 (come nel caso appena illustrato); questa valutazione è fatta da ogni zona in maniera autonoma e indipendente facendo la differenza tra il valore della temperatura letta dal sensore associato alla zona e il set point ambiente.

In seguito ogni zona “prende in prestito” dall’Integratore a cui è collegata (che in questo caso non svolge una vera funzione, ma “presta” semplicemente delle impostazioni) il valore dell’uscita 0/10V che corrisponde alla velocità che ha già determinato. 

Questo valore viene trasmesso sull’uscita 0/10 associata ad ogni zona (nel caso in cui alla zona non sia associato un Integratore, lo 0/10 della zona trasmette il relativo set point ambiente).

Management > 8 fan coils by 0/10V

...

This value is transmitted on the 0/10 output associated with each zone (if the zone is not associated with an Integrator, the 0/10 of the zone transmits the relative room set point of that zone).

1. Definizione degli offset di Integrazione in Configurazione 2

Come nel caso con meno di 8 fan coil è necessario definire gli offset di integrazione in Configurazione 2. Si ipotizzi di utilizzare gli stessi offset dell’esempio precedente.

Definition of Integration offset in Configuration 2

As in the case with less than 8 fan coils, it is necessary to define integration offset in Configuration 2. Assume to use the same offset as in the previous example.

2. Definizione delle stanze e dei gruppi di velocità di fan coil

Si ipotizzi di avere 10 stanze ognuna delle quali viene riscaldata e raffrescata da 1 fan coil, che vengono associati alla zona nella colonna Integrazione:

Definition of room and fan coil speed groups

Assume having 10 rooms, each of which is heated and cooled by 1 fan coil, which are associated with the zone in the Integration column:

PHOTO TBD

Il Sistema REG può gestire al massimo 8 gruppi di velocità di fan coil, visto che 8 sono le unità di Deumidificazione/Integrazione disponibili a cui appoggiarsi, quindi nel caso in esame è necessario individuare due coppie di stanze in cui ragionevolmente si possono gestire con le stesse velocità fan coil che non si trovano nello stesso ambiente, nell’esempio si definisce:

...

Soggiorno e Ingresso → Integrazione 1 (1 fan coil per ciascuna zona)

...

Cucina → Integrazione 2 (1 fan coil)

...

Camera 1 → Integrazione 3 (1 fan coil)

...

Camera 2 → Integrazione 4 (1 fan coil)

...

Camera 3 → Integrazione 5 (1 fan coil)

...

Sala da Pranzo → Integrazione 6 (1 fan coil)

...

Bagno 1 e Bagno 2 → Integrazione 7 (1 fan coil per ciascun bagno)

...

The REG System can manage maximum 8 fan coil speed groups, as 8 are the available Dehumidifier/Integration units to rely on, therefore in the case at hand it is necessary to identify two pairs of room in which, reasonably, it is possible to manage with the same speed fan coils which are not in the same room, in the example are defined:

  • Living Room and Hall → Integration 1 (1 fan coil for each zone)

  • Kitchen → Integration 2 (1 fan coil)

  • Room 1 → Integration 3 (1 fan coil)

  • Room 2 → Integration 4 (1 fan coil)

  • Room 3 → Integration 5 (1 fan coil)

  • Dining Room → Integration 6 (1 fan coil)

  • Bathroom 1 e Bathroom 2 → Integration 7 (1 fan coil for each bathroom)

  • Study → Integration 8 (1 fan coil)

Note

In questo esempio non è previsto che unità di deumidificazione/integrazione possano essere utilizzate per altro (ad esempio una VMC). Ma nel caso in cui le unità di deumidifica e integra disponibili fossero meno di 8 è necessario unificare il più possibile i fan coil che hanno la stessa mappatura tra velocità e volt. Quindi se si ipotizza che due unità di deumidifica/integra siano già impegnate i 10 fan coil dell’esempio potrebbero essere raggruppati come segue:

...

  • le Portate d’aria dell’Integrazione in % da 0 a 100 in bassa, media e alta velocità

PHOTO TBD

Le portate d’aria possono essere tutte diverse in base alle esigenze del singolo gruppo di velocità di fan coil. Ad esempio nella camera 1 le portate sono più basse rispetto al gruppo Soggiorno/Ingresso:

PHOTO TBD

Se due zone si appoggiano alla stessa unità di Integrazione per prendere il valore 0/10 di velocità non è detto che la velocità a cui vengono gestiti i fan coil sia la stessa.

...

Nella pagina Uscite REGDIN le Uscite Analogiche da collegare ai 10 fan coil non sono più le velocità di ciascun deumidificatore (utilizzato come Integrazione), ma il valore 0/10 trasmesso da ogni singola zona, che corrisponde al valore 0/10 della velocità (alta/media/bassa definita dalla zona) presa dall’unità di integrazione associata alla zona stessa:

PHOTO TBD

Quindi nella pagina Uscite REGDIN si associa ad esempio:

...

Un impianto di questo tipo necessita di molte uscite 0/10V (tante quante sono i fan coil installati), quindi si consiglia di utilizzare i moduli REG-IOC, che hanno 2 uscite analogiche 0/10V ciascuno e possono essere impostati nella pagina Uscite IO/B dal numero 92 a 99:

PHOTO TBD

Attenzione

Attualmente anche se viene mostrato il valore NC (Non Configurato) le funzione è comunque attiva, per verificare il voltaggio in uscita è necessario utilizzare un tester.

...

Ad esempio se la zona 10 (Studio) avesse 2 fan coil la pagina Uscite IO/B dedicherebbe 2 uscite analogiche alla zona 10:

PHOTO TBD

E' evidente che in questo caso essendo il sensore ambiente lo stesso, le uscite UA2/94 e UA1/95 avranno sempre lo stesso valore e i due fan coil lavoreranno alla stessa velocità.