The REG system allows you to control System Activation (switching on/off) and Current Season (summer/winter) based on 4 factors:

  • Control via User Setting    

    • using the parameters Heat/Cool Enable and Current Season Set (that can also be changed via Touch Screen, Remote Control, etc.), the user can activate the system and decide its current season.

  • Programming an Annual Schedule (see ANNUAL SCHEDULE)

    • Up to 8 dates can be set: for each it is possible to program the operating mode of air conditioning (off/summer/winter) and of domestic hot water production.

    • This mode is addressed to systems in which the system operating is programmed in advance, either by the user or by an external operator.

    • For example, it is possible to create a program such as:

      • October 15: activates heating in winter mode, activates DHW production;

      • December 20: activates heating in winter mode, switch off DHW production;

      • January 10: activates heating in winter mode, activates DHW production;

      • April 15: switch off the heating system, activates DHW production;

      • July 15: activates air conditioning in summer mode, activates DHW production;

      • September 15: switch off air-conditioning system, activates DHW production;

  • Configurazione di Segnali esterni di abilitazione (vedere SEGNALI ESTERNI):

    • Si possono configurare sino a 5 ingressi digitali (abilitazione/stagione/abilitazione estiva/abilitazione invernale/abilitazione acs) tramite i quali è possibile determinare la modalità di funzionamento tramite segnali digitali (contatti puliti) che vengono da comandi o apparecchiature esterne (interruttori, pompe di calore, ecc.).

    • E' una modalità utile quando si vuole che l'impianto interagisca con altri dispositivi e si adatti automaticamente

    • Ad esempio, è possibile fare in modo che

      • Cambiando la modalità di lavoro (estate/inverno) su una Pompa di Calore, anche il sistema REG cambi il proprio modo di lavoro.

      • Collegare l'impianto ad un sistema di allarme, in modo che quando si inserisce l'allarme si spenga la produzione di a.c.s. e/o la climatizzazione.

      • L'attivazione dell'impianto e la stagione di lavoro vengano controllate da un sistema domotico di terze parti.

  • Controllo tramite Temperatura esterna (vedere TEMPERATURA ESTERNA)

  • E' possibile programmare delle soglie di temperatura esterna per abilitare l'impianto in modalità estiva o in modalità invernale; è anche possibile fare in modo che l'impianto cambi automaticamente il modo di lavoro (Estate/Inverno) in base alla temperatura esterna.

  • Ad esempio è possibile:

  • In modalità inverno, spegnere l'impianto quando la temperatura esterna supera i 21°C, e riaccenderlo quando scende sotto i 19°C.

  • In modalità estate, spegnere l'impianto quanto la temperatura esterna scende sotto i 24°C, e riaccenderlo quando supera i 28 °C.

  • Commutare automaticamente l'impianto in modalità estiva quando la temperatura esterna sale sopra i 28°C ed in modalità invernale quando la temperatura esterna scende sotto i 19°C

    Configuration of Outdoor Enable Signals (see EXTERNAL SIGNALS):

    • Up to 5 digital inputs can be set (heat and cool enable/season/summer enable/ winter enable/ DHW enable) through which it is possible to determine the operating mode via digital signals (dry contacts) coming from controls or outdoor devices (switches, heat pump, etc.).

    • This is a useful mode when you want the system to interact with other devices and to adapt automatically.

    • For example, it is possible:

      • By changing the working mode (summer/winter) on a Heat Pump, the REG System also changes its working mode.

      • Connect the system to an alarm system, so that when the alarm is set, the DHW production and/or air-conditioning is switched off.

      • The activation of the system and the working season are controlled by a third-party home automation system.

  • Control via Outdoor Temperature (see OUTDOOR TEMPERATURE)

    • It is possible to program outdoor temperature thresholds to enable the system in summer or winter mode; it is also possible to have the system automatically changes its working mode (Summer/Winter) based on outdoor temperature.

    • For example, it is possible:

      • In winter mode, switch the system off when the outdoor temperature exceeds 21°C, and switch it on again when it drops below 19°C.

      • In summer mode, switch the system off when the outdoor temperature drops below 24°C, and switch it on again when it exceeds 28°C.

      • Automatically switch the system in summer mode when the outdoor temperature rises above 28°C, and in winter mode when the outdoor temperature falls below 19°C.

These 4 elements can work individually, or they can be combined to give maximum flexibility in managing the system; it is therefore possible to manage mixed situations, such as:

·        The system is switched on/off by the user via touch screen, but the choice of season (summer/winter) is automatically based on outdoor temperature.

·        The system is switched on/off via calendar; the user can still switch the system off via touch screen bypassing the predefined annual programming.

·        The system is switched on/off and the season is decided via calendar, but it is switched off automatically if the temperature exceeds preset limits.

Questi 4 elementi possono lavorare singolarmente, oppure possono essere combinati per dare la massima flessibilità nella gestione dell'impianto; e' quindi possibile gestire situazioni miste, quali ad esempio:

...

  1. Per primo viene considerato il Calendario Annuale:

    • Se non è abilitato, o se non è programmata nessuna data, si passa allo step 2 (Segnali esterni).

    • Se ci troviamo in una data per cui è stato specificato il modo di lavoro, il sistema si pone nel modo di lavoro specificato (estate/inverno); si passa direttamente allo step 6 (Verifica della temperatura esterna).

    • Se ci troviamo in una data per cui è stato specificato il modo di lavoro "automatico", si passa allo step 2 (Segnali esterni)

  2. Si considerano i Segnali esterni

    • Se nessuno tra i segnali stagione, abilitazione estiva, abilitazione invernale è configurato si passa allo step 3 (Tipo di impianto)

    • Se il segnale stagione è configurato viene letto (0ff=Inverno, On=Estate) ed il sistema si pone nel modo di lavoro richiesto; si passa direttamente allo step 6 (Verifica della temperatura esterna).

    • Se almeno uno tra i segnali di abilitazione invernale, abilitazione estiva è configurato viene/vengono letto/i ed in il sistema si pone nel modo di lavoro richiesto; si passa direttamente allo step 6 (Verifica della temperatura esterna).

  3. Si considera il Tipo di impianto (Solo Inverno/Solo Estate/Inverno+Estate):

    • Se l'impianto è del tipo Solo Inverno o Solo Estate il sistema si pone nel modo di lavoro consentito e si passa direttamente allo step 6 (Verifica della temperatura esterna).

    • Se l'impianto è del tipo Inverno+Estate si passa allo step 4 (Parametro impostazione stagione).

  4. Si considera il Parametro impostazione stagione, che l'utente può modificare da app, da web o dal touch screen:

    • Se impostato su Estate o su Inverno il sistema si pone nel modo di lavoro richiesto e si passa direttamente allo step 6 (Verifica della temperatura esterna).

    • Se impostato su Automatico si passa allo step 5. (Temperatura Esterna).

  5. Si considera la Temperatura Esterna:

    • Se la sonda esterna è non configurata o in errore l'impianto va in modalità Inverno

    • Se la sonda esterna rileva una temperatura sotto una certa soglia, l'impianto va in modalità Inverno

    • Se la sonda esterna rileva una temperatura sopra una certa soglia, l'impianto va in modalità Estate

  6. A questo punto la stagione è determinata; se è configurata la sonda esterna viene fatta una ulteriore verifica sulla Verifica della temperatura Esterna:

    • Se l'impianto è in modalità Inverno (determinata dagli step precedenti) ma la temperatura esterna è sopra una certa soglia, l'impianto viene spento.

    • Se l'impianto è in modalità Estate (determinata dagli step precedenti) ma la temperatura esterna è sotto una certa soglia, l'impianto viene spento.

Nota

Se tramite calendario o tramite segnali esterni si configura un modo di lavoro non valido per l'impianto (ad esempio se si programma una data di funzione Estate per un impianto che è stato configurato come Solo Invernale o viceversa), il sistema spegne la climatizzazione e si pone nel modo di lavoro consentito (Inverno, nell'esempio).

...

View file
nameInvalid file id - UNKNOWN_MEDIA_ID
pageANALOG AND DIGITAL INPUT MULTIPLEXER

Nota

La modalità vacanza non è attiva e non funziona.