Buffer tank Compensation Temperature can be used with all types of cascade algorithms (Parallel Function, POWER CASCADE e PID CASCADE ALGORITHM) since it is a standalone algorithm.
It does not affect the production of Domestic Hot Water in any way.
If the sensor in the buffer tank is not set to the Opentherm Heating/Cooling generators, the set point arriving from the switched on circuits will be passed directly (including the fixed offset that can be set for the sources).
This algorithm makes it possible to automatically compensate for any temperature losses due to the presence of heat exchangers or buffer tanks between the Opentherm generators and the circuits.
Il controllo utilizzato è PI (Proporzionale e Integrale), in questo caso l’errore è la differenza tra il set point che arriva dai circuiti e la temperatura letta del sensore secondario (più o meno la sua correzione):
Il coefficiente P moltiplica l’errore amplificandolo
Il coefficiente I tiene conto della variazione dell’errore nel tempo
Il risultato del calcolo PI è una correzione della temperatura richiesta ai generatori dai circuiti (in aumento o in diminuzione), tale risultato è il delta di temperatura riportato nella casella Corr. (°C) il quale non potrà mai superare la correzione massima in aumento o in diminuzione.
Nel momento in cui il sensore supera il set point più il delta Spegnimento la richiesta ai generatori viene sospesa, se invece il sensore scendo sotto il set point più il delta meno l’isteresi accensione la richiesta ai generatori viene ripristinata (se lasciati a zero non vengono considerati).