HEATING/COOLING OPENTHERM
In the OpenTherm page, in the “System Generators cascade control” it is possible to:
Enable the OpenTherm source in Winter, Summer, Off, Summer+Winter
Establish Priorities in relation to other Sources (see SOURCES PRIORITY)
Define what Outdoor temperature range it can operate in Winter and Summer
Define the limits of the water temperature in Heating
Define the limits of the water temperature in Cooling
In the “ Generators Demand Status” it is possible to see if the OpenTherm Heating/Cooling demand is active and with what set point (in the example above it is active and with 16°C set point).
Note
We generally speak of OpenTherm Heating because it was created to control boilers, but the protocol itself also implements the cooling part. Therefore, it is possible to manage also the heat pumps that implement this protocol.
In the “Generators” section at the bottom it is possible to select, for each of the 8 generators:
The Priority with which they are called if you choose to use the Cascade logic (PID CASCADE ALGORITHM, POWER CASCADE)
The Availability: Always, Only Heat, Only Cool.
If there is only one OpenTherm generator then the Priority of the generator is irrelevant, as well as the algorithm chosen for the cascade logic, it will always and only be the generator to start according to the priority assigned to the OpenTherm Source in the “System Generators cascade control”
Warning
G0 is to be used only if a DOT display is installed as master that has OpenTherm on board.
AVAILABLE DIGITAL OUTPUTS
OpenTherm has 4 digital outputs available
122. Active Request OT/H+C when request to OpenTherm is ON.
123. Active Request OT/DHW when the request to OpenTherm DHW is ON.
126. Active when at least one OpenTherm generator is in alarm.
127. Active when all OpenTherm generators are in alarm.