Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current Restore this Version View Page History

« Previous Version 7 Next »

The REG system devices require a 12 Vdc power supply and a BUS connection, therefore a total of 4 wires. The REG bus uses the EIA-485 standard (formerly known as RS-485), so the first choice is to use cables specifically created for this type of bus.

The ideal installation is given by a twisted and shielded cable specific for EIA-485 BUS, such as:

Note

These models are given as examples of cables that have the suitable electrical characteristics; the electrical designer will have to verify the compliance of the chosen cable with the specific needs of the system: type of installation, fire resistance, etc.; BELDEN in particular has a whole family of EIA-485 cables, suitable for any type of installation).

The use of this type of cable and compliance with the "IN-OUT" wiring is MANDATORY as shown in the following image:

PHOTO TBD

Furthermore, it is important to underline that:

  • the devices order (REG-DIN-8/REG-EXP-8/REG-TH etc.) is NOT important, they must not be connected in any particular order

  • each device must be addressed and there cannot be two components with the same address

  • if the address is changed using a dip switch to any of the components, the power supply must be switch OFF and then ON again for the new address to be acquired

  • being the MASTER, REG-DIN-8 has no address

  • the 12 Vdc power cable and the bus cable (A and B) must NOT share the electrical conduits with the 230 Vac

Attention

  • if a cable is actually used as indicated, the shielding (in the following drawing highlighted in blue) must be connected ONLY IN ONE POINT to the zero of the power supply and where the cable is interrupted, to allow the connection of the various devices (in the example below a REG-DIN-8, a REG-EXP-8, a REG-THL sensor and a REG-OTG), the shielding must be spliced, but NOT connected to anything:

PHOTO TBD

  • The BUS cable that connects the devices (master, I/O expansions, combined temperature and humidity sensors, displays) as mentioned before MUST be wired "in/out"; do not create backbones or star connections:

PHOTO TBD

if the installation needs do not allow for in-out wiring (houses on several floors for example) it is possible to install signal repeaters/splitters (code RIP-RS485) which allow the bus to be split correctly:

PHOTO TBD

  • The BUS cable must NOT be closed in a loop, it must ALWAYS be OPEN!

PHOTO TBD

  • alcuni impianti molto grandi potrebbero necessitare di più alimentatori, in questi casi i riferimenti (lo zero) di tutti gli alimentatori 12Vdc dell’impianto di termoregolazione devono essere corto circuitati:

PHOTO TBD

Nota

La scelta di avere più alimentatori può dipendere:

  • dal fatto che ci sono talmente tanti componenti dell’impianto che un solo alimentatore non potrebbe supportarli tutti

  • dal fatto che i componenti (pure non essendo molti) sono molto distanti e quindi la caduta di tensione lungo la linea è tale per cui bisogna mettere un secondo alimentatore all’altro capo

  • da entrambe le precedenti situazioni

Per quanto riguarda invece le dimensioni dei cavi per l’alimentazione:

  • Il dimensionamento dipende da come i vari elementi sono distribuiti lungo il bus, e quindi linee guida generali sono impossibili da dare

  • Infatti il problema non è la capacità dell’alimentatore, quasi sempre sovrabbondante, ma la caduta di tensione lungo la linea

  • Assumere il caso peggiore (tipo che tutta la corrente, 5A per il PS60 ad esempio, sia assorbita alla fine della linea, diciamo anche solo 30 metri) porta a situazioni irrealistiche, con cavi con sezioni assurdamente grandi

Se si vogliono dare delle indicazioni di massima ad esempio per un appartamento/piccola abitazione dove le espansioni e il master sono vicini e all’interno del quadro con il loro alimentatore e lungo la linea per l’appartamento ci sono solo sensori e display, si può considerare un’alimentazione da 2x1 mmq fino a 50 metri.

Per situazioni diverse (abitazioni molto grandi su più piani, espansioni sparse su diversi quadri/collettori)  sarebbe sempre opportuno far dimensionare questa parte da un progettista abilitato, che tenga conto di dove sono disposte le varie periferiche lungo la linea e di quanto ciascuna assorbe.