Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current Restore this Version View Page History

« Previous Version 4 Next »

REG System allows you to manage Thermal Solar Panels, for loading hot water into a tank.

In order to manage the system, the following temperature probes must be installed:

  • TS1: Solar panels probe (STA-type sensor for high temperature) - mandatory

  • TS2: Low part main tank probe (STM-type sensor) - mandatory

  • TS3: High part main probe (STM-type sensor) - optional

  • TS4: Medium part main probe (STM-type sensor) - optional

The structure of this configuration and the positioning of the probes refer to the diagram below:

The Solar function monitors the temperature of TS1 and TS2, when a temperature difference equal to P01: solar pump activation Threshold is detected, the system activates the associated pump. It remains active until at least two of the conditions below occurs:

  • The P02: solar pump deactivation Threshold is reached.

  • At least one of the two TS2 and TS3 probes reaches the maximum value of P03: Main tank high part max Temp or P04: Main solar tank maximum Temp.

Note that it is possible to control either both probes or only S2, by adjusting parameter P06: Sensor used for tank maximum temperature.

PHOTO TBD

per informazioni sull’impostazione dei sensori vedere ANALOG AND DIGITAL INPUT MULTIPLEXER

Il sistema è inoltre dotato dei seguenti parametri di Controllo/Protezione:

  • P07: Temperatura massima limite Collettore Solare, se TS1 supera tale valore viene spenta la pompa;

  • P08: Funzione raffreddamento Collettore Solare, se TS1 supera tale valore viene accesa la pompa fino al raggiungimento all'interno del bollitore  del valore di P15 o di una temperatura di 10 °C in meno rispetto al parametro P09: Funzione raffreddamento Bollitore. Tale meccanismo permette di scaricare il calore in eccesso  sul collettore all'interno del serbatoio;

  • P09: Funzione raffreddamento Bollitore, la quale permette l'attivazione della pompa del Collettore nel caso in cui la sonda TS3 è più alta rispetto al valore impostato E CONTEMPORANEAMENTE la temperatura sul collettore rilevata dalla sonda TS1 è più bassa di 20 °C rispetto a TS3. La pompa viene successivamente spenta nel momento  in cui la temperatura di TS3 scende al di sotto:

    • di un valore di temperatura pari a 10 °C in meno rispetto alla P10: Temperatura minima collettore;

    • della differenza tra le temperature TS1 e TS3, quando è inferiore a 10 °C

  • P10: Temperatura minima collettore, al di sotto di tale valore la pompa del Collettore Solare rimane spenta.

  • P12: Temperatura protezione antigelo circuito solare, al di sotto del quale viene attivata l'uscita per la protezione antigelo.

  • P15: Temperatura massima accumuli solari, superato il quale viene spenta la pompa (se attiva).

For information on sensor settings see ANALOG AND DIGITAL INPUT MULTIPLEXER.

The system is also equipped with the following Control/Protection parameters:

  • P07: Solar panels maximum temp limit, if TS1 exceeds this value the pump is switched off;

  • P08: Cooling solar panels function, if TS1 exceeds this value, the pump is switched on until the value of P15 or a temperature of 10°C less than the parameter P09: Cooling tank function is reached. This mechanism allows excess heat to be discharged to the manifold inside the tank.

  • P09: cooling tank function, which allows the activation of the manifold pump if the sensor TS3 is higher than the set value AND AT THE SAME TIME the temperature on the manifold detected by TS1 sensor is lower than 20°C than TS3. The pump is subsequently switched off when the temperature of TS3 drops below:

    • a temperature value of 10°C lower than P10: Solar panels minimum temperature;

    • the difference between TS1 and TS3 temperature, when it is less than 10°C

  • P10: Solar panels minimum Temperature, below this value the Solar Panel pump remains switched off.

  • P12: Solar panels Antifreeze temp protection. Below this value the antifreeze protection output is activated.

  • P15: Max Tem. Solar tanks, above which the pump is switched off (if active).

PHOTO TBD

Warning

Se la P08: Funzione raffreddamento Collettore Solare è stata attivata, la temperatura del Serbatoio può superare i valori settati dalla P03: Temperatura massima nella parte Alta del Bollitore principale, in ogni caso la pompa verrà disattivata nel momento  in cui viene raggiunto il P15:Temperatura massima accumuli solari, che è predominante su tutti gli altri e funge da limite di sicurezza per il Bollitore.

Le segnalazioni di Stato del sistema a cui bisogna  fare riferimento per monitorare il funzionamento sono i seguenti:

If P08: Cooling solar panels function has been activated, the tank temperature may exceed the values set by P03: main tank high part max Tem; in any case, the pump will be deactivated when P15: Max Tem. Solar tanks is reached, which is predominant over other factors and acts as a safety limit for the tank.

The System status signals that must be referred to in order to monitor the functioning are as follows:

 Codice Visualizzato

 Stato Pompa

Motivo

1

OFF

Il funzionamento della pompa è disabilitato dal parametro PS1

2

OFF

Raggiunta temperatura limite del collettore

3

OFF

Raggiunta temperatura limite dell'accumulo

4

OFF

Differenziale tra ST1 e ST2 insufficiente (minore di PS2)

5

OFF

Sonda ST1 Guasta

6

OFF

Raggiunta temperatura limite di sicurezza dell'accumulo

11

ON

Funzione raffreddamento collettore attiva

12

ON

Funzione antigelo collettore  attiva

13

ON

Funzione smaltimento calore accumulo

14

ON

Differenziale tra ST1 e ST2 maggiore di PS1

PHOTO TBD

AVAILABLE OUTPUTS

A digital output is available for the Solar Thermal single-tank:

·        98. Solar Function/Special 1 which is activated when the solar pump must operate (in the version prior to 4.32 the RegConfig  firmware it was called 98. Solar Pump)

USCITE DISPONIBILI

Per il Solare Termico monoaccumulo è disponibile l’uscita digitale:

  • 98. Funzione Solare/Speciale 1 _ che si attiva quando la pompa solare deve funzionare (nelle versioni precedenti la 4.32 del firmware del RegConfig si chiamava 98. Pompa Solare)

PHOTO TBD

Non esistono uscite analogiche associate alla funzione solare.

There are no analogue outputs associated with the solar function.