OBJECTIVE

This technical information details the new Power Cascade algorithm that can be selected within the OpenTherm page of the RegConfig Configurator.

CASCADE ALGORITHM FOR HEATING AND COOLING

The following image shows, within the OpenTherm page of the RegConfig, the position of the System Cascade Control Algorithm section and the Buffer Tank Compensation Temperature section:

The following image shows, within the OpenTherm page of the RegConfig, the position of the System Cascade control Algorithm section (red) and the Buffer tank Compensation Temperature section (blue), closely related to the PID cascade algorithm:

PHOTO TBD

The cascade algorithm can be of three types:

  • Parallel functioning: all OpenTherm generators enabled for heating and cooling are required to work simultaneously;

  • Power cascade: this control can be applied to those generators that are able to return the power output to RegConfig as data point, as the function aims to keep the enabled OpenTherm generators on within a certain power output range;

  • PID: stands for Proportional – Integral – Derivative. This last control allows you to switch on or off the enabled OpenTherm generators in relation to how close the temperature measured by a sensor (generally positioned in a buffer tank to which all the generators are connected) and the set point is.

Enabled OpenTherm generators are those generators that have a number (which can range from 1, highest priority, to 8, lowest priority) in the Generators section (highlighted in green) on the OpenTherm page and not OFF in the box corresponding to the “Heat/Cool” column. The number indicates the priority of the call, so in the image below G1 and G3 generators have priority 1 (they are called first), while G2 has priority 2 and G4 priority 3:

Warning

Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.

POWER CASCADE CONTROL ALGORITHM

The aim of the Power Cascade Control Algorithm is to ensure that the system has a water temperature as close as possible to the set point calculated by switching on the required number of generators and trying to make them work as efficiently as possible. To do this, it is necessary to know the power supplied by the generators, the % of power corresponding to the maximum efficiency of the generator, and the water outlet temperature of the generator.

To define when to switch a generator on/off, the algorithm compares the minimum power supplied between the active generator (and not degraded by the system) with the PotUp and PotDown parameters (which will be illustrated below) after a settable minimum time has passed during which no change is made to the number of switched on generators, to allow the active generators to go full speed.

The addition or switching off of a generator must always observe the following 3 parameters:

  • N. Start Generators: indicates the number of generators that are switched on starting from the condition “all OpenTherm generators are off”. For example, let us assume that the Start generators number is 2: you are in the condition “all OpenTherm generators are off” and the cascade algorithm results in only one generator switched on, but at least two generators are switched on at the same time. After switch-on (and therefore at least after the time indicated by “Stop between changes”) the algorithm may assess if the number of generators is appropriate to the demand of the system (and therefore leave it unchanged) or decrease or increase it; the number of generators at the start is useful if there are systems with many generators. Let us suppose we have a system with 8 generators: if the system starts with only one generator and then every “Stop between changes” (typically 3 minutes) adds another one, it will pass at least 21 minutes before the system goes at full speed; instead, if we set the initial number at 4, the system starts immediately with 4 generators, and then we decide if increase this number (and, in any case, in 12 minutes it would go to the maximum) or decrease it. 

  • N. Minimum Generators: indicates the minimum number of active generators. If, for example, it is set to 3 and 3 generators are currently active, even if the cascade algorithm were to determine the need to switch off a further generator, none would be switched off; in another way, they would have never less than 3 generators on (Note: this means that the REG System enables 3 generators which can then decide to switch off the flame/compressor, because they determine that their water outlet temperature is satisfied).

  • N. Maximum Generators: indicates the maximum number of generators that can be switched on at the same time. If 5 generators are enabled, but the maximum number is 3, this means that the algorithm can switch on maximum 3 generators, even though 4 would be needed. This choice has the direct consequence that the set point may never be reached or that may be reached but over a long period of time.

Once the number of start/minimum/maximum has been defined, it is necessary to define the following parameters:

  • Stop between changes (s): the variation is the change corresponding to the switching on or off of an OpenTherm generator. The pause between two variations it the minimum time that passes between the switching on or off of an OpenTherm generator and its subsequent switching on (or subsequent switching off) of another OpenTherm generator. For example, if at time x a generator is switched on, for the time indicated in the Stop between changes box, the algorithm will not add or remove generators (even though the result of the calculation would require it) to give the switched-on generators time to get up to speed and see the effects on the system;

  • PotUp [%]: among all the switched-on boilers (with flame and heating on), ignoring those that maybe are degraded and those that are not producing DHW, the lowest power output value (in %) is compared with PotUp: if higher, another generator is switched on. Usually set at 50%. If only one generator is switched on, the only power output will be compared with PoutUp. It must not be forgotten that any limits given by the number of generators start/minimum/maximum must be always respected, so for example if there is a system with 8 generators enabled, but the maximum number of generators is 6, the system will call the various generators in rotation, but it will never switch on more than 6 generators at the same time even though the algorithm would require it;

  • PotDown [%]: among all the switched-on boilers (with flame and heating on), ignoring those that maybe are degraded and those that are not producing DHW, the lowest power output value (in%) is compared with PotDown: if lower, the first boiler that had been switched on is switched off. Usually set at 30%. If only one boiler is switched on, the only power output is compared with PotDown. Even in this case, the system can keep removing generators, but it will never drop below the start generator number, unless the heating demand from the zones stops;

  • Gap [%]: represents the maximum power range that can be between the generator working less and the one working more, usually set at 8%. This parameter is useful to make the switched-on generators work at, more or less, the same power. So, if the minimum power expressed between the switched-on generators is 25% and Gap is 8%, all the generators are limited to 33% (=Maximum Power).

Attention: the powers are expressed in percentage, so if generators of different power are present, for example 24 kW and 35 kW, the same % power corresponds to a different real power. Moreover, some boilers give the real power output, so they consider 0% with boiler off, while with the flame on the power value read by the system is ≥ 15-17%, that is the minimum power at which they can modulate; other boilers instead indicate the % in relation to the useful regulation range, so with 0% they indicate that the boiler is working at the minimum of its modulation (probably 15-20% of the power rating), but still on. This may have an impact on the setting (although usually not a big one): for the former the minimum power = 30% probably indicates an actual 30%, while in the latter case the minimum power = 30% probably indicates roughly an actual 40% value, assuming its minimum is 15%, this would be [(100%-15%)*0,3+15%)];

  • Idle: this parameter (that means inactive) is the lower limit of the power limitation; a generator is never limited to a power lower than Idle. So, if the minimum power output between the switched-on generators is 5% and Gap is 8%, the maximum power would be 13%, but if Idle is 30%, then the generators will be limited at 30%. This parameter is essential when a new generator is switched on. Let us assume that we have switched on 2 generators that are both roughly 45% power. The minimum power output between the generators exceeds 50% (PotUp) and the system calls a third one, which starts at 0% power. If the Gap parameter is 8%, it means that between the generator expressing the minimum power and the one expressing the maximum power there can be a difference of at most 8%. So, if the third generator is at 0%, the others should be at 8%! To avoid this, a lower limit is put on the power of the already active generators, for example 30% (Idle). So, even if the generators that are switched on should stay at 8% power to conform to the Gap parameter, they will go to the set Idle value. 

MANAGEMENT OF DEGRADED GENERATORS

Two (non-mandatory) parameters are left to be set:

  • Power degraded

  • Temperature degraded

If left at zero, the algorithm does not manage degraded generators.

A generator is considered degraded if:

  1. The stop time is passed (that is the conditions during the pause following the addition/removal of a boiler are not considered);

  2. A generator is in heating or cooling demand (the DHW production is not considered);

  3. The power to which the generator is limited is bigger than the power degraded.

  4. The generator water outlet temperature is lower than the set point required of the generator less the temperature degraded (T water outlet < set point – temperature degraded, where the latter is a temperature delta K and not an absolute value). For example, if the set point is 40°C and the degraded temperature is 5 K, the generator temperature must drop below 35°C before it can be degraded, as long as the other four points also occur;

  5. The generator power output is lower that the “Power degraded” (which is an absolute power and not a power delta). For example, if the power degraded is 20%, the power output of the generator must drop below 20% before it can be degraded, as long as the other four points also occur.

Se un generatore viene degradato il sistema lo esclude da tutti i calcoli illustrati (calcolo potenza minima, potenza massima per confronto con PotUp, PotDown, Gap e Idle).

l risultato delle impostazioni effettuate è visualizzato nella parte in alto a destra della pagina OpenTherm “Stato Richiesta Generatori”:

PHOTO TBD

  • Abilita Set/Riscaldamento: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti non sta arrivando nessuna richiesta a OpenTherm.

  • Abilita Set/Sanitario: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto per la produzione di Acqua calda Sanitaria. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti o dalla pagina ACS non sta arrivando nessuna richiesta a OpenTherm.

  • Numero Generatori attivi (cascata): indica quanti generatori sono stati attivati per la cascata in riscaldamento (non per la produzione ACS).

  • l’ultimo rettangolo in basso (riquadro giallo) è il countdown della pausa tra variazioni in centesimi di secondo.

PHOTO TBD

Facendo sempre riferimento all'immagine relativa alla sezione Generatori della pagina OpenTherm:

PHOTO TBD

si fa presente quanto segue:

  • la produzione di Acqua Calda Sanitaria non risponde all'algoritmo di cascata di potenza;

  • l’algoritmo di cascata accende i generatori OpenTherm in base alla priorità inserita.

Nella parte inferiore della pagina OpenTherm si riporta per ogni generatore il risultato delle richieste di riscaldamento e ACS (riquadro rosso) e il feedback dai generatori verso il sistema REG (giallo):

PHOTO TBD

Evidenziato in rosso si trova:

  • la richiesta di R = Riscaldamento, A = ACS;

  • la temperatura richiesta in riscaldamento [°C];

  • la potenza in riscaldamento [%] è il limite superiore ed è il maggiore tra Idle e la minore delle potenze delle caldaie attive più il gap.

Se il generatore viene chiamato per la sola produzione ACS sia la temperatura richiesta che la potenza sono a zero, i valori che vengono passati in caso di produzione ACS sono quelli che si visualizzano in Stato Richiesta Generatori (in alto a destra nella pagina OpenTherm).

La pagina OpenTherm può gestire caldaie mediante protocollo OpenTherm. In giallo si evidenziano i valori trasmessi dalla caldaia strettamente legati a come il produttore dei generatori ha implementato il protocollo OpenTherm sulla caldaia stessa (fare sempre riferimento alla documentazione del generatore a riguardo). Passando con il mouse sopra i vari rettangoli/quadrati compare un tag con una descrizione estesa:

  • Stato Generatore: indica in che stato si trova il generatore (G = guasto, R = riscaldamento, SA = Acqua sanitaria, F = fiamma, S = service, ecc.). Se non implementato nessun quadrativo verrà popolato con le spunte.

  • Temperatura mandata, Temperatura ritorno, Temperatura ACS [°C]: sono le letture dei sensori del generatore se presenti.

  • Pot.: potenza erogata dal generatore in % (fare riferimento al manuale del produttore della caldaia).

  • Errore OT: errori Opentherm più frequenti (Ra = richiesta assistenza, Rr = reset remoto abilitato, Bp = Bassa pressione acqua, ecc.).

  • Errore OEM: indicazione del numero dell’errore, fare riferimento al manuale del generatore per la diagnostica.

  • Reset: reset dell’errore, funziona solo se la caldaia lo gestisce, fare riferimento al manuale del generatore per la diagnostica.

ROTAZIONE

A parità di priorità l’accensione segue l’ordine numerico dei generatori per la prima accensione, mentre per le successive accensioni i generatori vengono fatti ruotare:

PHOTO TBD

Quindi nell’esempio sopra riportato alla prima accensione l’ordine sarà:

G1 → G3 → G2 → G4

Alla seconda accensione:

G3 → G1 → G2 → G4

Attenzione: la produzione di Acqua Calda Sanitaria non risponde all'algoritmo di cascata di potenza.