To use this function, it is necessary at least to have installed firmware version 4.29 on the REG-DIN-8 and to use a RegConfig version 4.29 or later.
...
If the zones are served by the same duct unit, associate each zone with the same dehumidifier. In the example below, the first is associated with all zones:
...
Still remaining in the Zones page, enter Configuration Zone/2 and enter a value from 0 to 100 in the box indicated according to the weight of the individual room:
...
Move to the Dehumidifiers (D1) page and set the Integration control to “Active if requested” in summer and/or winter according to the needs of the system. Concerning Air Flows settings, the medium speed is ignored:
...
The current speed of the 0/10V output is the sum of the flow of the individual zones that refer to the dehumidifier 1, in the example above 1530+15+30 45 = 6075, therefore 6V7,5V.
If the sum were less than 30 10 or greater than 90100, the 0/10V would be limited to 3 1 V or 9 10 V.PHOTO TBD
...