To use this function, it is necessary at least to have installed firmware version 4.29 on the REG-DIN-8 and to use a RegConfig version 4.29 or later.

...

  1. Enter Configuration/2 and set the activation offset for the Integration function

...

  1. Go to the Zones page and create the desired zones (in the example, 3 zones have been created) by associating a room probe or sensor. Then, in the Integration column, choose the sum referring to one of the 4 available dehumidifiers (∑D1, ∑D2, ∑D3, ∑D4), in the example the first has been chosen:

...

  1. If the zones are served by the same duct unit, associate each zone with the same dehumidifier. In the example below, the first is associated with all zones:

...

  1. Still remaining in the Zones page, enter Configuration Zone/2 and enter a value from 0 to 100 in the box indicated according to the weight of the individual room:

...

  1. Move to the Dehumidifiers (D1) page and set the Integration control to “Active if requested” in summer and/or winter according to the needs of the system. Concerning Air Flows settings, the medium speed is ignored: 

...

The current speed of the 0/10V output is the sum of the flow of the individual zones that refer to the dehumidifier 1, in the example above 1530+15+30 45 = 6075, therefore 6V7,5V.

If the sum were less than 30 10 or greater than 90100, the 0/10V would be limited to 3 1 V or 9 10 V.PHOTO TBD

...