This avoids wasting cold water (contained in the pipes) while waiting for hot water to arrive from the storage tank. It would also be a waste not to have a timer associated with the re-circulation, in fact in this case the re-circulation water pump would always be switched on with a consequent increase in electricity consumption.

Re-circulation pipe can be inserted either in the storage tank or directly on the cold sanitary water inlet of the thermostatic mixer, the choice depending on various factors (availability of connections on the storage tank, available space):

...

Il sistema REG gestisce il ricircolo nativamente mediante orologio e in particolare mediante l’orologio associato al sottosistema ACS:

...

Nel momento in cui l’orologio ACS è in modalità Comfort il ricircolo si attiva, attivando l’uscita digitale 50 che deve dare il consenso al circolatore di ricircolo:

...

Se si vuole svincolare l’orologio del ricircolo dall’orologio dell’ACS è necessario creare una zona che funga da ricircolo, quindi all’interno della pagina Zone si associa una zona libera ad un orologio (non associare collettori, deumidificatori o integrazione):

...

Ricordarsi di impostare come Modo Speciale di lavoro della zona dedicata al ricircolo in Configurazione Zone/3 il modo ACS:

...

L’orologio può essere impostato come segue:

...

Inoltre è possibile affinare il controllo del ricircolo aggiungendo una sonda di temperatura dell’acqua sulla tubazione di ricircolo di modo che il circolatore parta negli orari indicati dall’orologio, ma solo se la temperatura della sonda è scesa sotto un certo valore (ad esempio 38°C):

...

Si procede quindi associando una sonda alla zona dedicata al ricircolo come nell’immagine precedente e si impostano i set point nella pagina Parametri Zona:

...

Impostando 38°C significa che solo sotto i 38°C (e negli orari di accensione dell’orologio) la zona sarà attiva e accenderà il circolatore di ricircolo che deve essere associato all’uscita della zona stessa, nell’esempio riportato la zona 1:

...

non si deve utilizzare l’uscita 50 in questo caso.

Infine il ricircolo si spegnerà sia se si è fuori dagli orari impostati, ma anche quando la temperatura della sonda supera il set point impostato (38°C) più l’isteresi impostata nella pagina ACS:

...

nell’esempio riportato l’isteresi di primo stadio è 5 K, quindi il ricircolo potrebbe spegnersi anche quando la sonda rileva una temperatura maggiore di 43°CThe REG System manages re-circulation by default through timetable and particularly through the timetable associated with the DHW subsystem:

...

When the DHW timetable is in Comfort mode, the recycle is activated, triggering digital output 50, which must give consent to the re-circulation water pump:

...

If you want to release the re-circulation timetable from the DHW timetable, you must create a zone to act as a circulation, then on the Zones page associate a free zone with a timetable (do not associate circuit, dehumidifiers or integration):

...

Remember to set the DHW mode as work Special Mode of the zone dedicated to the re-circulation water pump in Configuration Zone / 3:

...

The timetable can be set as indicated below:

...

It is also possible to refine the re-circulation control by adding a water temperature probe to the re-circulation pipe so that the circulation starts at the times indicated by the timetable, but only if the probe temperature is below a certain value (for example, 38°C):

...

Then you proceed by associating a probe to the circulation zone as in the previous image and set the set point on the Zone Parameters page:

...

Setting 38°C means that only below 38°C (and at the times when the timetable is turned on) the zone will be active and turn on the re-circulation water pump, which must be associated with the output of the zone itself, in the example shown is the zone 1:

...

Output 50 must not be used in this case.

Finally, the circulation will be switched off either you are outside the set times, and also when the probe temperature exceeds the set point (38°C) plus the hysteresis set in the DHW page:

...

In the example shown the hysteresis is 3 K, therefore the circulation could switch off even when the probe detects a temperature higher than 41°C.