To use this function, it is necessary to have at least firmware version 4.30 on the REG-DIN-8 and to use a RegConfig version 4.30 or later.
...
The REG System provides up to 8 Dehumidifier/Integration units, therefore, if in a system there are up to 8 fan coils, in as many rooms it is possible, for each zone, to manage a fan coil, using the Dehumidifiers page used as Integration, independently. For example, if there are 4 zones each with a fan coil for heating and cooling (or only cooling), each zone will be associated with a Dehumidifier in the Integration column:
PHOTO TBD
...
In the Dehumidifier page, on each sub page D1, D2, D3 e D4 verranno impostati:
Comando integrazione “Attivo se richiesto” in estate e in inverno (se la stanza deve essere sia raffrescata che riscaldata)
Comando valvola “Attivo se richiesto” se il Collettore viene associato nella pagina Deumidificatori, se viene associato nella pagina Zone il Comando valvola può essere lasciato spento
“Collettore associato” se gestito dalla pagina Deumidificatori
i valori in % delle velocità bassa, media e alta delle portate di Integrazione
PHOTO TBD
La velocità bassa, media o alta di ciascun fan coil dipende dagli offset di integrazione impostati in Configurazione 2:
PHOTO TBD
Quindi se la differenza tra la temperatura letta dal sensore di ciascuna zona e il set point impostato supera 1 K la velocità del fan coil sarà bassa, se supera 2 K sarà media e se supera 3 K sarà alta.
Nella pagina Uscite REGDIN le Uscite Analogiche da collegare ai 4 fan coil sono le velocità di ciascun deumidificatore (utilizzato come Integrazione) indipendente l’una dall’altra:
PHOTO TBD
Nel caso in cui i fan coil siano più di 8 non è più possibile seguire questa strada.
Gestione > 8 fan coil mediante 0/10V
In questo caso la zona determina la propria velocità (alta/media/bassa) sempre facendo riferimento ai valori di offset in Configurazione 2 (come nel caso appena illustrato); questa valutazione è fatta da ogni zona in maniera autonoma e indipendente facendo la differenza tra il valore della temperatura letta dal sensore associato alla zona e il set point ambiente.
In seguito ogni zona “prende in prestito” dall’Integratore a cui è collegata (che in questo caso non svolge una vera funzione, ma “presta” semplicemente delle impostazioni) il valore dell’uscita 0/10V che corrisponde alla velocità che ha già determinato.
Questo valore viene trasmesso sull’uscita 0/10 associata ad ogni zona (nel caso in cui alla zona non sia associato un Integratore, lo 0/10 della zona trasmette il relativo set point ambiente).
1. Definizione degli offset di Integrazione in Configurazione 2
Come nel caso con meno di 8 fan coil è necessario definire gli offset di integrazione in Configurazione 2. Si ipotizzi di utilizzare gli stessi offset dell’esempio precedente.
2. Definizione delle stanze e dei gruppi di velocità di fan coil
Si ipotizzi di avere 10 stanze ognuna delle quali viene riscaldata e raffrescata da 1 fan coil, che vengono associati alla zona nella colonna Integrazione:
PHOTO TBD
Il Sistema REG può gestire al massimo 8 gruppi di velocità di fan coil, visto che 8 sono le unità di Deumidificazione/Integrazione disponibili a cui appoggiarsi, quindi nel caso in esame è necessario individuare due coppie di stanze in cui ragionevolmente si possono gestire con le stesse velocità fan coil che non si trovano nello stesso ambiente, nell’esempio si definisce:
Soggiorno e Ingresso → Integrazione 1 (1 fan coil per ciascuna zona)
Cucina → Integrazione 2 (1 fan coil)
Camera 1 → Integrazione 3 (1 fan coil)
Camera 2 → Integrazione 4 (1 fan coil)
Camera 3 → Integrazione 5 (1 fan coil)
Sala da Pranzo → Integrazione 6 (1 fan coil)
Bagno 1 e Bagno 2 → Integrazione 7 (1 fan coil per ciascun bagno)
Studio → Integrazione 8 (1 fan coil)
Nota
In questo esempio non è previsto che unità di deumidificazione/integrazione possano essere utilizzate per altro (ad esempio una VMC). Ma nel caso in cui le unità di deumidifica e integra disponibili fossero meno di 8 è necessario unificare il più possibile i fan coil che hanno la stessa mappatura tra velocità e volt. Quindi se si ipotizza che due unità di deumidifica/integra siano già impegnate i 10 fan coil dell’esempio potrebbero essere raggruppati come segue:
...
Soggiorno e Ingresso → Integrazione 1 (1 fan coil per ciascuna zona)
...
Cucina → Integrazione 2 (1 fan coil)
...
Camera 1 / 2 / 3 → Integrazione 3 (1 fan coil per ogni camera)
...
Bagno 1 e Bagno 2 → Integrazione 4 (1 fan coil per ciascun bagno)
...
, and D4 will be set:
Integration control “Active if requested” in summer and winter (if the room is to be both heated or cooled)
Valve control “Active if requested” if the Circuit is associated in the Dehumidifier page, if it is associated in the Zone page the Valve control may be left off
“Associated circuit” if managed from the Dehumidifiers page
The values in % of the low, medium, and high speeds of the Integration flow rates
...
Low, medium, or high speed of each fan coil depends on the integration offset set in Configuration 2:
...
Therefore, if the difference between the temperature read by the sensor of each zone and the set point set exceeds 1 K, the fan coil speed will be low, if it exceeds 2 K it will be medium and if it exceeds 3 K it will be high.
In the REGDIN OUTPUT page, the Analog Outputs to be connected to the 4 fan coils are the speeds of each dehumidifier (used as Integration) independent of each other:
...
If the fan coils are more than 8, it is no longer possible to follow this path.
Management > 8 fan coils by 0/10V
In this case, the zone determines its own speed (high/medium/low) always referring to the offset values in Configuration / 2 (as in the case just illustrated): this evaluation is made by each zone autonomously and independently by making the difference between the value of the temperature read by the sensor associated with the zone and the room set point.
Then, each zone “borrows” from the Integrator to which it is connected (which in this case does not perform a proper function, but it simply “lends” settings) the value of the 0/10V output that corresponds to the speed it has already determined.
This value is transmitted on the 0/10 output associated with each zone (if the zone is not associated with an Integrator, the 0/10 of the zone transmits the room set point of that zone).
1. Definition of Integration offset in Configuration 2
As in the case with less than 8 fan coils, it is necessary to define integration offset in Configuration 2. Assume to use the same offset as in the previous example.
2. Definition of room and fan coil speed groups
Assume having 10 rooms, each of which is heated and cooled by 1 fan coil, which are associated with the zone in the Integration column:
...
The REG System can manage maximum 8 fan coil speed groups, as 8 are the available Dehumidifier/Integration units to rely on, therefore in the case at hand it is necessary to identify two pairs of room in which, reasonably, it is possible to manage with the same speed fan coils which are not in the same room, in the example are defined:
Living room and Hallway → Integration 1 (1 fan coil for each zone)
Kitchen → Integration 2 (1 fan coil)
Room 1 → Integration 3 (1 fan coil)
Room 2 → Integration 4 (1 fan coil)
Room 3 → Integration 5 (1 fan coil)
Dining Room → Integration 6 (1 fan coil)
Bathroom 1 e Bathroom 2 → Integration 7 (1 fan coil for each bathroom)
Studio → Integration 8 (1 fan coil)
Note
In this example it is not provided which dehumidifier/integration units can be used for anything else (e.g., a ventilation unit). But, if the available dehumidification/integration unit are less than 8, it is necessary to unify as much as possible the fan coil that have the same mapping between speed and volts. Therefore, if it is assumed that two dehumidification/integration units are already occupied, the 10 fan coils in the example could be grouped as follows:
Living room and Hall → Integration 1 (1 fan coil for each zone)
Kitchen → Integration 2 (1 fan coil)
Room 1 / 2 / 3 → Integration 3 (1 fan coil for each zone)
Bathroom 1 e Bathroom 2 → Integration 4 (1 fan coil for each zone)
Dining Room → Integration 5 (1 fan coil)
Studio → Integrazione Integration 6 (1 fan coil)
è infatti ragionevole ipotizzare che stanze con la stessa destinazione d’uso possano condividere la stessa mappatura di velocità dei fan coil.
3. Impostazione dei gruppi di velocità dei fan coil
Nel gruppo di velocità di fan coil che fanno capo al deumidificatore 1 nella pagina Deumidificatori D1 è necessario impostare solamente:
le Portate d’aria dell’Integrazione in % da 0 a 100 in bassa, media e alta velocità
PHOTO TBD
Le portate d’aria possono essere tutte diverse in base alle esigenze del singolo gruppo di velocità di fan coil. Ad esempio nella camera 1 le portate sono più basse rispetto al gruppo Soggiorno/Ingresso:
PHOTO TBD
Se due zone si appoggiano alla stessa unità di Integrazione per prendere il valore 0/10 di velocità non è detto che la velocità a cui vengono gestiti i fan coil sia la stessa.
Prendiamo ad esempio la zona Soggiorno e Ingresso dall’immagine al punto 2 si nota che:
...
It is reasonable to assume that rooms with the same intended use can share the same fan coil speed mapping.
3. Setting the fan coil speed groups
In the fan coil speed group of dehumidifier 1 on the Dehumidifier D1 page, it is only necessary to set:
The Air Flow Rate of the Integration in % from 0 to 100 in low, medium and high.
...
The Air Flow Rate can all be different depending on the requirements of the individual fan coil speed group. For example, in Room 1 the flow rates are lower than in the Living/Hall group:
...
If two zones rely on the same Integration unit, to take the 0/10 speed value, it is not certain that the speed at which the fan coils are operated are the same.
Let us take the example of the Living Room and Hall zone from the image; in point 2 we can notice that:
The temperature read by the sensor in the Living Room is 28,2°C with set point 27°C → delta = 1,9 Kla temperatura letta dalla sonda nell’Ingresso è 30°C con 2 K
The temperature read by the probe in the Hall is 30°C with set point 25,5°C → delta = 4,5 K
quindi il fan coil del Soggiorno andrà a velocità bassa Therefore, the Living Room fan coil will run at low speed (4 V - – 40%) perché il delta è compreso tra because the delta is between 2 (medium speed offset di media velocità) > 1,9 2 K > 1 K (low speed offset di bassa velocità), mentre il fan coil dell’ingresso andrà a velocità alta whereas the Hall fan coil will run at high speed (9 V - – 90%) perché il because the delta è is 4,5 K > 3 K (high speed offset di alta velocità).
4. Assegnare le uscite Assigning 0/10V Outputs
Nella pagina Uscite REGDIN le Uscite Analogiche da collegare ai 10 fan coil non sono più le velocità di ciascun deumidificatore (utilizzato come Integrazione), ma il valore 0/10 trasmesso da ogni singola zona, che corrisponde al valore 0/10 della velocità (alta/media/bassa definita dalla zona) presa dall’unità di integrazione associata alla zona stessa:
PHOTO TBD
Quindi nella pagina Uscite REGDIN si associa ad esempioOn the REGDIN Outputs page, the Analog Outputs to be connected to the 10 fan coils are no longer the speeds of each dehumidifier (used as Integration), but the 0/10 value transmitted from each individual zone, corresponding to the 0/10 value of the speed (high/medium/low defined by the zone) taken from the integration unity associated with the same zone:
...
Therefore, on the REGDIN Outputs page, is associated with, for example:
UA1/0: set point zona zone 1 (Soggiorno) da collegare all’ingresso 0/10V del fan coil del Soggiorno Living Room) to be connected with the 0/10 V input of the fan coil of the Living Room
UA2/0: set point zona zone 2 (Cucina) da collegare all’ingresso 0/10V del fan coil della CucinaKitchen) to be connected with the 0/10 V input of the fan coil in the Kitchen
UA1/1: set point zona zone 3 (Camera Room 1) da collegare all’ingresso 0/10V del fan coil della Camera to be connected with the 0/10 V input of the fan coil in the Room 1
UA2/1: set point zona zone 4 (Camera Room 2) da collegare all’ingresso 0/10V del fan coil della Camera 2
Un impianto di questo tipo necessita di molte uscite 0/10V (tante quante sono i fan coil installati), quindi si consiglia di utilizzare i moduli REG-IOC, che hanno 2 uscite analogiche 0/10V ciascuno e possono essere impostati nella pagina Uscite IO/B dal numero 92 a 99:
PHOTO TBD
Attenzione
Attualmente anche se viene mostrato il valore NC (Non Configurato) le funzione è comunque attiva, per verificare il voltaggio in uscita è necessario utilizzare un tester.
...
to be connected with the 0/10 V input of the fan coil in the Room 2
A system of this type requires many 0/10 outputs (as many as the installed fan coils); therefore, it is advisable to use the REG-IOC modules, which have two 0/10V analogue outputs each and can be set in the IO/B Output page from number 92 to 99:
...
Warning
Currently, even if the NC (Not Configured) value is shown, the function is still active; to check the output voltage it is necessary to use a tester.
You can find an example preset attached:
View file | ||
---|---|---|
|
Infine se in una stanza è presente più di un fan coil, è sufficiente ripetere quanto illustrato fino a qui, semplicemente bisogna associare a più uscite analogiche (in base a quanti fan coil ci sono) il valore 0/10 della zona/stanza che ha più fan coil.
Ad esempio se la zona 10 (Studio) avesse 2 fan coil la pagina Uscite IO/B dedicherebbe 2 uscite analogiche alla zona 10:
PHOTO TBD
E' evidente che in questo caso essendo il sensore ambiente lo stesso, le uscite UA2/94 e UA1/95 avranno sempre lo stesso valore e i due fan coil lavoreranno alla stessa velocitàFinally, if there is more than one fan coil in a room, it is enough to repeat what has been shown so far, simply associate the 0/10 value of the zone/room that has more fan coils with more analogue outputs (depending on how many fan coils there are).
For example, if the zone 10 (study) had 2 fan coils, the IO/B Output page would dedicate 2 analogue outputs to zone 10:
...
It is obvious that, in this case, since the room sensor is the same, UA2/94 e UA1/95 outputs will always have the same value and the two fan coils will work at the same speed.