Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Each zone can be associated with a Dehumidifier, either for dehumidification or integration function, from the Configuration Zone/1 sub page:

...

If the zone is linked to a Temperature and Humidity Sensor (see ANALOG AND DIGITAL INPUT MULTIPLEXER) and if the zone is in Comfort or Economy mode (so in the Status column of the Zone Page is Comfort or Economy), the system compares the humidity measured in the zone with the humidity set point set via the Set Relative Humidity parameter in the Zones Parameters sub page: if the measured humidity is higher than the set point, the dehumidifier corresponding to the zone is activated.

Note

Zone temperature control logic is independent from the humidity control logic: a zone can be fulfilled in temperature, but not in humidity. In this case, the main output of the zone will be off, but the associated dehumidifier will be on. The opposite is also true.

...

A dehumidifier can be associated with several zones: in this case the dehumidifier is activated if even only one of the associated zones requires its intervention.

Attenzione

Ogni zona ha un proprio set di umidità, quindi non è detto che la zona che fa partire il deumidificatore sia quella con l'umidità più alta in assoluto; se per esempio:

  • La Zona 1, associata al Deumidificatore 1, ha un set di umidità al 50% e rileva una umidità del 52%

  • La Zona 2, associata al Deumidificatore 1, ha un set di umidità al 60% e rileva una umidità del 58%

il Deumidificatore 1 sarà attivato su richiesta della Zona 1, seppure questa rilevi una umidità più bassa di quella della zona 2.

Isteresi nella logica di accensione/spegnimento dei deumidificatori

L'algoritmo di accensionde dei deumidificatori è dotato di isteresi, per prevenire rapide accensioni e spegnimenti del deumidificatore quando l'umidità impostata è vicina alla soglia impostata.

Nel dettaglio:

  • Il deumidificatore viene attivato quando l'umidità relativa è maggiore o uguale al Set di umidità relativa della zona

  • Il deumidificatore viene spento quando l'umidità relativa è inferiore al Set di umidità della zona - il valore del parametro globale Isteresi dell'umidità di zona .

Se, per esempio, il set di umidità è 55.0% e il parametro globale Isteresi dell'umidità di zona è 3%:

  • Il deumidificatore si attiva se l'umidità è maggiore o uguale al 55.0%

  • Il deumidificatore si spegne se l'umidità è inferiore a 52.0% (quindi quando arriva a 51.9%)

per maggiori informazioni vedere https://setecna.atlassian.net/wiki/spaces/PUBDOCS/pages/3258778593.

Esempio di attivazione del Deumidificatore

Nel seguito verrà riportato un esempio illustrativo del funzionamento del deumidificatore e dell'attivazione dell'output associato.

...

Zone associate a deumidificatori SENZA sensore di Umidità

Anche una zona dotata di un sensore di sola temperatura (senza cioè misura dell'umidità) può essere associata ad un deumidificatore; in questo caso la zona non controlla il deumidificatore (cioè non ne comanda mai l'accensione), ma usa il deumidificatore come "tramite" per valutare la possibile formazione di condensa; per maggiori dettagli vedere https://setecna.atlassian.net/wiki/spaces/PUBDOCS/pages/3258778841Warning

Each zone has its own humidity set, so it is not necessary that the zone that starts the dehumidifier is the one with the highest humidity; if, for example:

  • Zone 1, associated with Dehumidifier 1, has a humidity set at 50% and detects a humidity of 52%

  • Zone 2, associated with Dehumidifier 1, has a humidity set at 60% and detects a humidity of 58%

Dehumidifier 1 will be activated at the request of Zone 1, even though it detects a lower humidity than that of zone 2.

Hysteresis in the on/off logic of dehumidifiers

The algorithm of dehumidifier’s ignition is equipped with hysteresis to prevent rapid on/off of the dehumidifier when the set humidity is close to the set threshold.

In detail:

  • The dehumidifier is activated when the relative humidity is greater than or equal to the Zone Relative Humidity Set

  • The dehumidifier is deactivated when the relative humidity is lower than the Zone Humidity Set – the value of the global parameter Zone Humidity Hysteresis.

If, for example, the humidity set is 55.0% and the Hysteresis global parameter of the humidity zone is 3%:

  • The dehumidifier turns on if the humidity is greater than or equal to 55.0%

  • The dehumidifier turns off is the humidity is lower than 52.0% (therefore when it reaches 51.9%).

For more information, see ZONE SET POINT AND SENSOR SETTING.

Example of Dehumidifier activation

The following is an illustrative example of dehumidifier operation and associated output activation.

...

Zones associated with dehumidifiers WHITOUT a humidity sensor

A zone equipped with a temperature-only sensor (that is without humidity measurement) can be associated with a dehumidifier; in this case, the zone does not control the dehumidifier (i.e., it never controls its ignition), but it uses the dehumidifier as a “vehicle” to assess the possible formation of condensation; for more details, see DEW POINT MANAGEMENT.