The annual calendar schedule can be ON or OFF and can be enabled or disabled from the Configuration/1 Page:

...

When the calendar is active, it contributes, together with other factors (see SYSTEM ACTIVATION AND SEASONAL CHANGE), to the activation of the system and the determination of Current Season.

Note

Il menù è visibile solo se la funzione Calendario Annuale è stata attivata, mettendo la spunta su Abilita Calendario.

Ciascuna voce permette di specificare il modo di lavoro dell'impianto a partire da una specifica data;  per ogni voce va impostata:

  • La data di partenza del periodo: a partire dalla data specificata vengono attivati i 2 parametri successivi, finchè non viene raggiunta la data successiva.

  • Stato di climatizzazione dell'impianto: può assumere i seguenti valori:

  • Stato della produzione di Acqua Calda Sanitaria; può assumere i seguenti valori:

    • OFF, la produzione ACS è spenta

    • ON, la produzione ACS è accesa

Attenzione

Anche l’ACS ha il suo comando di abilitazione da segnale esterno (vedere https://setecna.atlassian.net/wiki/spaces/PUBDOCS/pages/3258779972)

Nota

Il modo impostato in una certa data viene mantenuto fino alla data successiva, in senso cronologico, presente nel calendario. Se l’impianto non è online e quindi NON riceve data e ora dal server bisogna impostarlo manualmente The menu is only visible if the Annual Schedule function has been activated by ticking Schedule Enable.

Each entry allows you to specify the system working mode starting from a specific date; for each entry you must set:

  • The start date of the period: starting from the specified date, the next 2 parameters are activated, until the next date is reached.

  • Heating/Cooling system status: it can take on the following values:

    • OFF, the system is OFF;

    • WIN, the heating mode is ON; the Current Season is set to Winter

    • SUM, the cooling is ON; the Current Season is set to Summer

    • AUTO, the system is ON; the Current Season is automatically determined based on the outdoor temperature (OUTDOOR TEMPERATURE) or by an outdoor signal (EXTERNAL SIGNALS).

  • Domestic Hot Water production status; it can take on the following values:

    • OFF, the DHW production is OFF

    • ON, the DHW production is ON

Warning

DHW also has its own external signal enable command (see DHW SET POINT)

Note

The mode set on a certain date is maintained until the next date, chronologically, in the schedule. If the system is not online and therefore DOES NOT receive a date and time from the server, this must be set manually in DATE AND TIME SETTINGS.