Nel seguito verranno riportati due grafici esemplificativi sulle modalità di Intervento della sonda di Temeperatura Esterna nella logica di attivazione/disattivazione dell'impianto.
Esempio 1
La sonda di Temperatura Esterna non è utilizzata come selettore della stagione (Estate/Inverno), ma funge solamente da parametro di controllo per l'attivazione/disattivazione dell'impianto; i parametri dovranno essere settati come di seguito indicato:
Below there are two example diagrams about the Intervention mode of the Outdoor Temperature probe in the system’s activation/deactivation logic.
Example 1
The Outdoor Temperature probe is not used as season selector (Summer/Winter), but it only serves as a control parameter for the activation/deactivation of the system; the parameters must be set as indicated below:
...
Annual Schedule → There are two seasonal ranges, winter (01/10 - 01/05) e una estiva and summer (01/05 - 01/10)
Imposta Stagione -> Auto
Tipo di Impianto -> Estate/Inverno
Canale abilitazione Impianto -> Non configurato
Canale abilitazione Estiva -> Non configurato
Canale abilitazione Invernale -> Non configurato
Canale seleziona Stagione -> Non configurato
Canale Temperatura Esterna -> Secondo esigenze impianto
...
Come è possibile notare, la selezione della stagione viene gestita mediante calendario annuale e la temperatura esterna serve solamente per attivare/disattivare l'impianto in base ai valori assunti dalla temperatura esterna (l'impianto viene spento se la temperatura è troppo alta in Inverno o troppo bassa in Estate).
Esempio 2
La sonda di Temperatura Esterna determina sia l'impostazione della stagione che funge da parametro di controllo per l'attivazione/disattivazione dell'impianto.
Calendario Annuale -> Non configurato
Imposta Stagione -> Auto
Tipo di Impianto -> Estate/Inverno
Canale abilitazione Impianto -> Non configurato
Canale abilitazione Estiva -> Non configurato
Canale abilitazione Invernale -> Non configurato
Canale seleziona Stagione -> Non configurato
Canale Temperatura Esterna -> Secondo esigenze impianto
...
In questo caso la selezione della stagione viene gestita totalmente dalla Sonda di Temperatura Esterna, dal momento che l'impianto commuta automaticamente dall'Inverno all'Estate nel momento in cui la Temperatura Esterna supera la soglia per l'estate, che nel nostro caso è impostata a 24 °C.
Canale delle sonda esterna
.
Set Season → Auto
System Type → Summer/Winter
Enable Heat/Cool Channel → Not configured
Enable Summer Channel → Not configured
Enable Winter Channel → Not configured
Enable Season Channel → Not configured
Outdoor Temperature Channel → According to system requirements
...
As you can see, the season selection is managed through the annual schedule and the outdoor temperature is only used to activate/deactivate the system according to the values assumed by the outdoor temperature (the system is switched off if the temperature is too high in Winter or too low in Summer).
Example 2
The Outdoor Temperature probe determines the season setting and it works as a control parameter for switching the system on/off.
Annual Schedule → Not configured
Set Season → Auto
System Type → Summer/Winter
Enable Heat/Cool Channel → Not configured
Enable Summer Channel → Not configured
Enable Winter Channel → Not configured
Enable Season Channel → Not configured
Outdoor Temperature Channel → According to system requirements
...
In this case, the selection of the season is entirely managed by the Outdoor Temperature Probe, since the system automatically switches from Winter to Summer when the Outdoor Temperature exceeds the threshold for summer, which in our case is set at 24°C.
Outdoor Temperature Channel
It is possible to set the channel of the outdoor probe in Configuration/1 (see ANALOG AND DIGITAL INPUT MULTIPLEXER):
...
Sempre Also, in Configurazione/1 si possono impostare le soglie per l’inverno e per l’estate e la stagione come Inverno, Estate o Automatico.
La lettura della sonda esterna si può vedere in basso a sinistra nella pagina Configurazione Zona/1.
Attenzione
Se non si vuole che la sonda esterna giochi un ruolo nell’attivazione/disattivazione dell’impianto allora impostare una soglia per l’Inverno molto alta (30°C) e una soglia per l’estate molto bassa (5°C). Se anche non si vuole che intervenga per il cambio stagionale allora non impostare Automatico per la stagione, ma scegliere Estate o Inverno.
Taratura della sonda di temperatura esterna
Questo parametro è accessibile direttamente da REG-DIN-8 o tramite i touch screen, non da remoto o via RegConfig.
Altrimenti impostare come Canale Sonda Esterna una Funzione matematica differenza tra la temperatura letta dalla sonda e una costante (vedere https://setecna.atlassian.net/wiki/spaces/PUBDOCS/pages/3258780561Configuration/1, the thresholds for winter and summer and the season as Winter, Summer, or Automatic can be set.
The outdoor probe reading can be seen in the bottom left corner of the Zone/1 Configuration page.
Warning
If you don’t want that the outdoor probe play a role in activating/deactivating the system, then set a very high winter threshold (30°C) and a very low summer threshold (5°). If you also don’t want that it changes the season then do not set Automatic for the season, but choose Summer or Winter.
Calibration of the outdoor temperature probe
This parameter is accessible directly from REG-DIN-8 or via the touch screens, not from the remote control or via RegConfig.
Otherwise, set a Mathematical function difference between the temperature read by the probe and a constant as the Outdoor Temperature Channel (see MATH FUNCTIONS).