The REG system devices require a 12 Vdc power supply and a BUS connection, therefore a total of 4 wires. The REG bus uses the EIA-485 standard (formerly known as RS-485), so the first choice is to use cables specifically created for this type of bus.
...
BELDEN, 9841 (see https://www.belden.com/products/Cable/Electronic-Wire-Cable/RS-485-Cable)
CEAM, CPR 6003
TASKER, C521
FANTON, ACS 9841
NoteQuesti
modelli sono dati come esempio di cavi che hanno le caratteristiche elettriche idonee; il progettista elettrico dovrà verificare la rispondenza del cavo scelto alle specifiche esigenze dell'impianto: tipo di posa, resistenza al fuocoThese models are given as examples of cables that have the suitable electrical characteristics; the electrical designer will have to verify the compliance of the chosen cable with the specific needs of the system: type of installation, fire resistance, etc.; la BELDEN in particolare dispone di tutta una famiglia di cavi particular has a whole family of EIA-485 , adatti a qualsivoglia tipologia installativa).L'uso di questo tipo di cavo ed il rispetto del cablaggio “ENTRA-ESCI” è OBBLIGATORIO come riportato nella seguente immagine:cables, suitable for any type of installation).
The use of this type of cable and compliance with the "IN-OUT" wiring is MANDATORY as shown in the following image: