REG System allows you to manage Thermal Solar Panels, for loading hot water into a tank.

...

Note that it is possible to control either both probes or only S2, by adjusting parameter P06: Sensor used for tank maximum temperature.

PHOTO TBD

per informazioni sull’impostazione dei sensori vedere ANALOG AND DIGITAL INPUT MULTIPLEXER

...

  • P07: Solar panels maximum temp limit, if TS1 exceeds this value the pump is switched off;

  • P08: Cooling solar panels function, if TS1 exceeds this value, the pump is switched on until the value of P15 or a temperature of 10°C less than the parameter P09: Cooling tank function is reached. This mechanism allows excess heat to be discharged to the manifold inside the tank.

  • P09: cooling tank function, which allows the activation of the manifold pump if the sensor TS3 is higher than the set value AND AT THE SAME TIME the temperature on the manifold detected by TS1 sensor is lower than 20°C than TS3. The pump is subsequently switched off when the temperature of TS3 drops below:

    • a temperature value of 10°C lower than P10: Solar panels minimum temperature;

    • the difference between TS1 and TS3 temperature, when it is less than 10°C

  • P10: Solar panels minimum Temperature, below this value the Solar Panel pump remains switched off.

  • P12: Solar panels Antifreeze temp protection. Below this value the antifreeze protection output is activated.

  • P15: Max Tem. Solar tanks, above which the pump is switched off (if active).

PHOTO TBD

Warning

Se la P08: Funzione raffreddamento Collettore Solare è stata attivata, la temperatura del Serbatoio può superare i valori settati dalla P03: Temperatura massima nella parte Alta del Bollitore principale, in ogni caso la pompa verrà disattivata nel momento  in cui viene raggiunto il P15:Temperatura massima accumuli solari, che è predominante su tutti gli altri e funge da limite di sicurezza per il Bollitore.

...

The System status signals that must be referred to in order to monitor the functioning are as follows:

 Codice Visualizzato

 Stato Pompa

Motivo Displayed Code

 Pump Status

Explanation

1

OFFIl

funzionamento della pompa è disabilitato dal parametro Pump operation is disabled by parameter PS1

2

OFFRaggiunta temperatura limite del collettore

Solar Panels threshold temperature reached

3

OFFRaggiunta temperatura limite dell'accumulo

Tank temperature threshold reached

4

OFF

Differenziale tra Differential between ST1 e and ST2 insufficiente insufficient (minore di less than PS2)

5

OFF

Sonda Faulty ST1 GuastaProbe

6

OFFRaggiunta temperatura limite di sicurezza dell'accumulo

Tank safety temperature threshold reached

11

ONFunzione raffreddamento collettore attiva

Panels cooling function active

12

ONFunzione antigelo collettore  attiva

Panels antifreeze function active

13

ONFunzione smaltimento calore accumulo

Tank heat disposal function

14

ON

Differenziale tra Differential between ST1 e and ST2 maggiore di greater than PS1

PHOTO TBD

AVAILABLE OUTPUTS

A digital output is availablefor the Solar Thermal Panels single-tank:·       

  • 98. Solar Function/Special 1 which is activated when the solar pump must operate (in the version prior to 4.32 the RegConfig  firmware it was called 98. Solar Pump)

...

Per il Solare Termico monoaccumulo è disponibile l’uscita digitale:

  • 98. Funzione Solare/Speciale 1 _ che si attiva quando la pompa solare deve funzionare (nelle versioni precedenti la 4.32 del firmware del RegConfig si chiamava 98. Pompa Solare)

PHOTO TBDNon esistono uscite analogiche associate alla funzione solare.

There are no analogue outputs associated with the solar function.