Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

The DHW can or cannot be associated with a timetable and a sensor, to which it is possible giving a calibration:PHOTO TBD

...

for sensor setting information see ANALOG AND DIGITAL INPUT MULTIPLEXER, while for timetable setting see TIMETABLES.

...

The Hysteresis corresponds to the DHW shutdown delta. Therefore, if we assume that we want 60°C 55°C and we have a hysteresis of 5°C3°C, the request to the associated circuit, and consequently to the generator, will start if the temperature drops below 60°C 55°C and stops above 65°C58°C.

The Delta Aux Output is what activates the auxiliary output of the DHW, which could be an integration booster heater or another source. If we take the above example again, the auxiliary output starts if the water temperature drops (either in Comfort or Economy) below 50°C (55°C (60°C-5°C).

PHOTO TBD

The DHW work mode can be forced in Economy, Comfort, or in Antifreeze mode. If it is left in automatic, it will follow the associated timetable, if present, or the indicated mode (Comfort in this example):

PHOTO TBD

The Force Output, on the other hand, is to be used during testing (or temporarily to solve problems that require it).

Warning

The Force Work Mode has priority over timetable forcing. Therefore, if the associated timetable is in Force Economy mode while the DHW is in Force Comfort mode, then the Work Mode will be in Comfort mode.

...

  • 48. DHW Activation_ which activates below the Comfort of Economy set point and deactivates when the DHW temperature > set point + hysteresis

  • 49. DHW AUX. Activation_ which activates if the DHW temperature < set point – delta aux output

PHOTO TBD

The only analogue output is the DHW set point itself:

PHOTO TBD