Which sources to enable at any given time depends on the following factors:

...

The position of the 6 parameters listed above is shown in the following screenshot:

PHOTO TBD

Warning

Do not use the Auxiliary sensor!

...

If it is used to control Enabling, besides the above points being true (the source must be in the season and outdoor temperature ranges in which it is enabled, it must have the correct priority, the enable signal if present must be entered and the block signal not entered), the sensor used must be in the water set point range set in the "Set point Control" section (in the case below in the range 20-55°C):

PHOTO TBD

The source will be enabled as long as the sensor is > the minimum set - delta (in the example 20°C - 5°C, so up to 15°C) and as long as it is < the maximum set + hysteresis (in the example 55°C + 5°C, so up to 60°C).

...

If it is used to control Activation, the source must still be enabled, otherwise it will never be activated (the source must be in the season and outside temperature range in which it is enabled, it must have the correct priority, the enable signal if present must be entered and the block signal not entered), but its activation or deactivation depends only on the set point being reached.

PHOTO TBD

L’attivazione e disattivazione della sorgente sono legate solo al Set Point che arriva dai circuiti (il più alto in inverno e il più basso in estate, offset inclusi). Se il set point fosse maggiore del massimo o minore del minimo verrebbe tagliato, quindi se arriva dai circuiti un set point di 70°C, al massimo viene passato 55°C.

Quindi ipotizzando di avere un set point di 55°C, la sorgente si attiva se il sensore < 55°C e si disattiva quando il sensore > set point + isteresi (quindi 51°C).

La sorgente resterà sempre abilitata a prescindere dalle temperature raggiunte dal sensore. Nel caso sopra riportato anche se il sensore è a 14°C, la sorgente è sempre abilitata.

L’uscita di attivazione ausiliaria, invece, si attiva se il sensore < set point - delta (quindi nel caso in esame sotto i 52°C = 55°C -3 °C) e si disattiva quando il sensore > set point - delta (quindi nel caso in cui il sensore superi i Activation and deactivation of the source are linked only to the set point arriving from the circuits (the highest in winter and the lowest in summer, including offsets). If the set point was higher than the maximum or lower than the minimum, it would be cut off, so if a set point of 70°C arrives from the circuits, a maximum of 55°C is set to the source.

So, assuming a set point of 55°C, the source will activate if the sensor < 55°C and deactivate when the sensor > set point + hysteresis (so 51°C). 

The source will always remain enabled regardless of the temperatures reached by the sensor. In the above case, even if the sensor is at 14°C, the source is always enabled.

The auxiliary activation output, on the other hand, is activated if the sensor < set point – delta (so in the case under consideration below 52°C = 55°C -3 °C) and is deactivated when the sensor > set point – delta (so in the case above 52°C).

Attivazione e Abilitazione senza Sensore Associato

...

Nell’ultima sezione in basso di ciascuna sorgente è riportato un riepilogo che a colpo d’occhio permette di capire se la sorgente è abilitata, attiva, in raffrescamento e se le temperature esterne e dell’acqua sono nei range di abilitazione della sorgente:

PHOTO TBD

Vi è anche un confronto tra la temperatura desiderata che arriva dai circuiti (set point) e la temperatura del sensore utilizzato, se presente (Temperatura Attuale).

...

From 56 to 59 are the same for source 2 and from 60 to 63 for source 3.

PHOTO TBD

AVAILABLE ANALOGUE OUTPUTS

...

For source 2 is the output 18, 19 for source 3.

PHOTO TBD