Which sources to enable at any given time depends on the following factors:
...
The position of the 6 parameters listed above is shown in the following screenshot:
PHOTO TBD
Warning
Do not use the Auxiliary sensor!
...
If it is used to control Enabling, besides the above points being true (the source must be in the season and outdoor temperature ranges in which it is enabled, it must have the correct priority, the enable signal if present must be entered and the block signal not entered), the sensor used must be in the water set point range set in the "Set point Control" section (in the case below in the range 20-55°C):
PHOTO TBD
La sorgente sarà abilitata fino a quando il sensore sarà > del set minimo - delta (nell’esempio The source will be enabled as long as the sensor is > the minimum set - delta (in the example 20°C - 5°C, quindi fino a 15°C) e fino a quando sarà < al set massimo + isteresi (nell’esempio so up to 15°C) and as long as it is < the maximum set + hysteresis (in the example 55°C + 5°C, quindi fino a so up to 60°C).
Fuori da queste temperature sarà disabilitata, come si vede dall’assenza delle spunte nell’ultima sezione “Stato Sorgente”, in quanto il sensore legge 65°C.
L’attivazione e disattivazione della sorgente sono invece legate al Set Point che arriva dai circuiti (il più alto in inverno e il più basso in estate, offset inclusi). Se il set point fosse maggiore del massimo o minore del minimo verrebbe tagliato, quindi se arriva dai circuiti un set point di 70°C, al massimo viene passato 55°C.
Quindi ipotizzando di avere un set point di 40°C (T. Desiderata), la sorgente si attiva se il sensore < 40°C e si disattiva quando il sensore > set point + isteresi (quindi 45°C). La sorgente resterà comunque abilitata fino a 60°C.
L’uscita di attivazione ausiliaria, invece, si attiva se il sensore < set point - delta (quindi nel caso in esame sotto i 35°C = 40°C -5 °C) e si disattiva quando il sensore > set point - delta (quindi nel caso in cui il sensore superi i Outside these temperatures it will be disabled, as you can seen by the absence of ticks in the last section “Source Status”, as the sensor reads 65°C.
The activation and deactivation of the source are instead linked to the Set Point arriving from the circuits (the highest in winter and the lowest in summer, offsets included). If the set point was higher than the maximum or lower than the minimum it would be cut off, so if a set point of 70°C arrives from the circuits, a maximum of 55°C is set for the source.
So, assuming a set point of 40°C (Desired T.), the source will activate if the sensor < 40°C and deactivate when the sensor > set point + hysteresis (so 45°C). The source will however remain enabled up to 60°C.
The auxiliary activation output, instead, is activated if the sensor < set point – delta (so in the case under consideration below 35°C = 40°C - 5°C) and it is deactivated when the sensor > set point – delta (so in the case the sensor is above 35°C).
2. Per controllare Attivazione
Se si utilizza per controllare l’Attivazione, la sorgente deve comunque risultare abilitata, altrimenti non si attiverà mai (la sorgente deve essere nella stagione e nel range di temperatura esterna in cui è abilitata, deve avere la priorità corretta, il segnale di abilitazione se presente deve essere inserito e il segnale di blocco non inserito), ma la sua attivazione o disattivazione dipende solo dal raggiungimento del set point.
PHOTO TBD
L’attivazione e disattivazione della sorgente sono legate solo al Set Point che arriva dai circuiti (il più alto in inverno e il più basso in estate, offset inclusi). Se il set point fosse maggiore del massimo o minore del minimo verrebbe tagliato, quindi se arriva dai circuiti un set point di 70°C, al massimo viene passato 55°C.
...
Nell’ultima sezione in basso di ciascuna sorgente è riportato un riepilogo che a colpo d’occhio permette di capire se la sorgente è abilitata, attiva, in raffrescamento e se le temperature esterne e dell’acqua sono nei range di abilitazione della sorgente:
PHOTO TBD
Vi è anche un confronto tra la temperatura desiderata che arriva dai circuiti (set point) e la temperatura del sensore utilizzato, se presente (Temperatura Attuale).
...
da 56 a 59 sono le stesse per la sorgente 2 e da 60 a 63 per la sorgente 3.
PHOTO TBD
USCITE ANALOGICHE DISPONIBILI
...
Per la sorgente 2 è l’uscita 18 e la 19 per la sorgente 3.
PHOTO TBD