Which sources to enable at any given time depends on the following factors:

...

The position of the 6 parameters listed above is shown in the following screenshot:

PHOTO TBD

Warning

Do not use the Auxiliary sensor!

...

If it is used to control Enabling, besides the above points being true (the source must be in the season and outdoor temperature ranges in which it is enabled, it must have the correct priority, the enable signal if present must be entered and the block signal not entered), the sensor used must be in the water set point range set in the "Set point Control" section (in the case below in the range 20-55°C):

PHOTO TBD

The source will be enabled as long as the sensor is > the minimum set - delta (in the example 20°C - 5°C, so up to 15°C) and as long as it is < the maximum set + hysteresis (in the example 55°C + 5°C, so up to 60°C).

...

The auxiliary activation output, instead, is activated if the sensor < set point – delta (so in the case under consideration below 35°C = 40°C - 5°C) and it is deactivated when the sensor > set point – delta (so in the case the sensor is above 35°C).

2.

...

To control Activation

If it is used to control Activation, the source must still be enabled, otherwise it will never be activated (the source must be in the season and outside temperature range in which it is enabled, it must have the correct priority, the enable signal if present must be entered and the block signal not entered), but its activation or deactivation depends only on the set point being reached.

PHOTO TBD

L’attivazione e disattivazione della sorgente sono legate solo al Set Point che arriva dai circuiti (il più alto in inverno e il più basso in estate, offset inclusi). Se il set point fosse maggiore del massimo o minore del minimo verrebbe tagliato, quindi se arriva dai circuiti un set point di 70°C, al massimo viene passato 55°C.

...

Nell’ultima sezione in basso di ciascuna sorgente è riportato un riepilogo che a colpo d’occhio permette di capire se la sorgente è abilitata, attiva, in raffrescamento e se le temperature esterne e dell’acqua sono nei range di abilitazione della sorgente:

PHOTO TBD

Vi è anche un confronto tra la temperatura desiderata che arriva dai circuiti (set point) e la temperatura del sensore utilizzato, se presente (Temperatura Attuale).

...

Per la parte di sorgente degradata fare riferimento a SORGENTE DEGRADATA.

USCITE DIGITALI DISPONIBILI

...

AVAILABLE DIGITAL OUTPUTS

The digital output available for the sources are:

  • 52. Sorgente Source 1 Abilitata Enable

  • 53. Sorgente Source 1 AttivaActive

  • 54. Sorgente Source 1 AusiliariaAuxiliary

  • 55. Sorgente Source 1 Ausiliaria negata (negato della funzione 54Auxiliary denied (function 54 denied)

da From 56 a 59 sono le stesse per la sorgente 2 e da 60 a 63 per la sorgente to 59 are the same for source 2 and from 60 to 63 for source 3.

PHOTO TBD

USCITE ANALOGICHE DISPONIBILI

...

AVAILABLE ANALOGUE OUTPUTS

The analogue output available for the source is:

  • 17. Sorgente Source 1:corrisponde alla temperatura desiderata, quindi al set point ricevuto dai circuiti it corresponds to the desired temperature, therefore to the set point received from the circuits (+/- gli offset), che può essere inviato alla sorgente se essa può ricevere un segnale which can be sent to the source if it can receive a 0/10 in ingresso di set point input signal.

Per la sorgente 2 è l’uscita 18 e la 19 per la sorgente For source 2 is the output 18, 19 for source 3.

PHOTO TBD