Water Pump Control
When a circuit is active (in Comfort, Economy, Antifreeze mode), the associated pump in the “Circuit Water Pump Management” section is switched on:
PHOTO TBD
It is possible to enter a delay between the time when the circuit is switched on and the time when the pump is switched on via the parameter Delay ON (seconds); for example, it is possible to enter a delay of a few minutes to allow the header of a manifold to open before the pump is switched on.
...
This graph illustrates the relationships between the time when the circuit is switched on/off, the switching on of the pumps, the switching on of the valve and the sources associated with the circuit:
PHOTO TBD
The individual pump is seen as PUMP A and it is possible, if the pump has one, to assign to an input of the REG or its I/O modules the pump block signal of the pump itself and configure it to Water Pump A Input Block (see ANALOG AND DIGITAL INPUT MULTIPLEXER).
...
If Single Pump Blk NC is chosen as pump type instead of Single Pump, the Pump Blocking input is reversed (from NO becomes NC, so closed no block, open block).
Controllo di Pompe Gemellari
Il sistema è in grado di gestire le pompe gemellari e anche in questo caso ci sono due opzioni:
P. Gemellari
P. Gemellare Blk NC
Anche per le pompe gemellari è possibile impostare degli ingressi digitali del sistema per rilevare se la pompa/le pompe sono in blocco. Nel caso delle pompe gemellari, la rilevazione del blocco oltre a registrare l'allarme provoca la commutazione sulla pompa gemella, preservando la funzionalità dell'impianto.
Se entrambe le pompe sono funzionanti (cioè nessuna delle due è in blocco), il sistema commuta automaticamente tra la pompa A e la pompa B ogni 4 giorni.
I parametri che determinano a quali ingressi sono collegati i segnali di allarme delle pompe sono:
Input di Blocco Pompa A : Ingresso digitale per rilevare il Blocco della Pompa A.
Input di Blocco Pompa B : Ingresso digitale per rilevare il Blocco della Pompa B.
Il modo in cui vengono interpretati tali ingressi dipende dall'impostazione del parametro P. Gemellari/P. Gemellare Blk NC.
Nota
E' possibile ottenere lo stesso risultato facendo l'inversione sull'ingresso digitale Input Blocco Pompa A, cioè al posto di mettere REG IA1 come nell’esempio, selezionare REG / IA1.
PHOTO TBD
Controllo Valvole Miscelatrici
...
Twin Pump Control
The system is able to manage twin pump and, again, there are two options:
Twin Pump
Twin Pump Blk NC
Even for twin pumps, it is possible to set digital inputs to the system to detect if the pump/pumps are blocked. In the case of twin pumps, the block detection not only registers the alarm, but also causes the switching to the twin pump, preserving the functionality of the system.
If both pumps are running (i.e. neither pump is blocked), the system automatically switches between pump A and pump B every 4 days.
The parameters that determine to which inputs the alarm signals of the pumps are connected are:
Water Pump A Input Block: Digital input to detect the Blocking of Pump A.
Water Pump B Input Block: Digital input to detect the blocking of Pump B.
The way these inputs are interpreted, depends on the setting of parameter P. Twin/P. Twin Blk NC.
Note
It is possible to achieve the same result by inverting the digital input Water Pump A Input Block: select REG / IA1 instead of REG IA1, as indicated in the example.
PHOTO TBD
Mixing Valve Control
Each Circuit/Manifold can manage a mixing valve with 3-point or 0/10V control.
PHOTO TBD
Valvole 0/10 V
Nel caso delle valvole 0/10V l’output PID è la posizione della valvola!
...
Per le Valvole a 3 punti è possibile considerare un tempo di arresto da impostare nella Pagina Configurazione 2, passato il quale viene rilasciato anche il relay di chiusura:
PHOTO TBD
Quindi se il tempo di arresto è 60 secondi, dopo questo periodo sia il relay valvola aperta che valvova chiusa saranno aperti, quindi non passerà più corrente al servomotore.
Per entrambe le valvole è possibile considerare una banda morta da impostare sempre in Configurazione 2:
PHOTO TBD
La banda morta (delta K) è un range entro il quale non vengono fatte correzioni all’output PID, ignorando sostanzialmente l’errore. Se è = 0 non viene considerata.
...
Una volta raggiunto l’allarme di sovratemperatura non basta che la sonda del circuito si raffreddi, bisogna anche spegnere e riaccendere l’impianto!
PHOTO TBD
I tempi indicati si sommano, quindi se si è inserito 10 secondi per ciascuno, se entro 30 secondi la temperatura non rientra sotto il massimo ammesso il sistema segnalerà per il circuito x l’allarme di sovratemperatura.
Attenzione
L’allarme di sovratemperatura si presenta anche se lo stesso circuito viene chiamato a lavorare contemporaneamente sia in riscaldamento sia in raffrescamento.
...
da 68 a 95 sono le stesse per i circuiti da 2 a 8.
PHOTO TBD
USCITE ANALOGICHE DISPONIBILI
...
da 2 a 8 sono la stessa per i circuiti da 2 a 8.
PHOTO TBD