To use this function, it is necessary to have at least firmware version 4.30 on the REG-DIN-8 and to use a RegConfig version 4.30 or later.
...
The REG System can manage maximum 8 fan coil speed groups, as 8 are the available Dehumidifier/Integration units to rely on, therefore in the case at hand it is necessary to identify two pairs of room in which, reasonably, it is possible to manage with the same speed fan coils which are not in the same room, in the example are defined:
Living Room room and Hallway → Integration 1 (1 fan coil for each zone)
Kitchen → Integration 2 (1 fan coil)
Room 1 → Integration 3 (1 fan coil)
Room 2 → Integration 4 (1 fan coil)
Room 3 → Integration 5 (1 fan coil)
Dining Room → Integration 6 (1 fan coil)
Bathroom 1 e Bathroom 2 → Integration 7 (1 fan coil for each bathroom)
Studio → Integration 8 (1 fan coil)
Note
In this example it is not provided which dehumidifier/integration units can be used for anything else (e.g., a ventilation unit). But, if the available dehumidification/integration unit are less than 8, it is necessary to unify as much as possible the fan coil that have the same mapping between speed and volts. Therefore, if it is assumed that two dehumidification/integration units are already occupied, the 10 fan coils in the example could be grouped as follows:
Living Room room and Hall → Integration 1 (1 fan coil for each zone)
Kitchen → Integration 2 (1 fan coil)
Room 1 / 2 / 3 → Integration 3 (1 fan coil for each zone)
Bathroom 1 e Bathroom 2 → Integration 4 (1 fan coil for each zone)
Dining Room → Integration 5 (1 fan coil)
Study Studio → Integration 6 (1 fan coil)
...
The Air Flow Rate can all be different depending on the requirements of the individual fan coil speed group. For example, in Room 1 the flow rates are lower than in the Living Room/Hall group:PHOTO TBD
...
If two zones rely on the same Integration unit, to take the 0/10 speed value, it is not certain that the speed at which the fan coils are operated are the same.
...
On the REGDIN Outputs page, the Analog Outputs to be connected to the 10 fan coils are no longer the speeds of each dehumidifier (used as Integration), but the 0/10 value transmitted from each individual zone, corresponding to the 0/10 value of the speed (high/medium/low defined by the zone) taken from the integration unity associated with the same zone:
PHOTO TBD
Therefore, on the REGDIN Outputs page, is associated with, for example:
...
A system of this type requires many 0/10 outputs (as many as the installed fan coils); therefore, it is advisable to use the REG-IOC modules, which have two 0/10V analogue outputs each and can be set in the IO/B Output page from number 92 to 99:
PHOTO TBD
Warning
Currently, even if the NC (Not Configured) value is shown, the function is still active; to check the output voltage it is necessary to use a tester.
...
For example, if the zone 10 (study) had 2 fan coils, the IO/B Output page would dedicate 2 analogue outputs to zone 10:
PHOTO TBD
It is obvious that, in this case, since the room sensor is the same, UA2/94 e UA1/95 outputs will always have the same value and the two fan coils will work at the same speed.