Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

The REG System can manage controlled mechanical ventilation (CMV) units both via timetable and via VOC sensor and via a combination of both.

...

VOC sensor (code REG-AQ-Sxx) must be configured with the address from 8A to 8F (as indicated in the product data sheet) without set (s/set) as it has no display and associated with a dedicated zone for renewal within the Zones – Configuration Zone/1 page; furthermore, the ventilation unit must be associated as integration unit:PHOTO TBD

...

 This special zone manages temperature and humidity in different way:

  • In temperature there are the ppm (parts per million) of CO2, so if you read 40 that’s 400 ppm.

  • In humidity you can see the VOC parameters in ppb (parts per billion), then if you read 30 that’s 300 ppb of VOC. This is true for the old VOC sensor REG-AQ-SXX, while for the new REG-AQ40-SXX this value is not present.

  • The humidity set point is the hysteresis (multiplied by a factor of 10) of threshold switching between Economy/OFF and Comfort/Economy

  • Comfort and Economy set point are thresholds, so if I exceed the Economy threshold the CMV starts at Economy speed, if i exceed Comfort it starts in Comfort, to switch to lower speed it must drop below the threshold – the hysteresis.

...