Introduction
Each zone can send two types of requests to Dehumidifiers:
...
The Dehumidifier subsystem can also manage three digital outputs and/or a 0/10 output for fan speed control: the output is activated together with the integration contact, and can take 3 values corresponding to low, medium, and high speed: among all the integration requests from various zones (each of which specifies if it wants a low, medium, or high integration see INTEGRATION OFFSET) the subsystem determines the highest request and applies it to the output (digital or analogue).PHOTO TBD
...
The voltage levels corresponding to the 3 speeds can be set freely, and independently for each Dehumidifier; when the integration contact is switched-off, the output switches to 0 V and all digital outputs are open.
...
The Dehumidifier subsystem can be associated with a manifold/circuit; if associated, the circuit is activated when the valve control and at least one between dehumidification and integration control is active.
Note
If also or only the integration control is active, the circuit is activated in COMFORT mode.
if only the dehumidification control is active, the circuit is activated in ECONOMY mode.
Finally, both the dehumidifier and integration can activate a father dehumidifier and/or father integration, which will be activated at the same time:PHOTO TBD
...
In Actual Status (bottom right of the page) it is possible to see the active functions.
...
96. Dehumidifier 1 - switching dehumidification demand on and off
100. Dehumidifier 2 - switching dehumidification demand on and off
104. Dehumidifier 3 - switching dehumidification demand on and off
108. Dehumidifier 4 - switching dehumidification demand on and off
112. Dehumidifier 5 - switching dehumidification demand on and off
116. Dehumidifier 6 - switching dehumidification demand on and off
120. Dehumidifier 7 - switching dehumidification demand on and off
124. Dehumidifier 8 - switching dehumidification demand on and off
160. Integration 1 - switching integration demand on and off
161. Integration 2 - switching integration demand on and off
162. Integration 3 - switching integration demand on and off
163. Integration 4 - switching integration demand on and off
164. Integration 5 - switching integration demand on and off
165. Integration 6 - switching integration demand on and off
166. Integration 7 - switching integration demand on and off
167. Integration 8 - switching integration demand on and off
97. Valve 1 - switching the valve on and off
101. Valve 2 - switching the valve on and off
105. Valve 3 - switching the valve on and off
109. Valve 4 - switching the valve on and off
113. Valve 5 - switching the valve on and off
117. Valve 6 - switching the valve on and off
121. Valve 7 - switching the valve on and off
125. Valve 8 - switching the valve on and off
129/130/131. Low/Medium/High Dehumidifier 1 - Low, medium, and high speed switch
133/134/135. Low/Medium/High Dehumidifier 2 - Low, medium, and high speed switch
137/138/139. Low/Medium/High Dehumidifier 3 - Low, medium, and high speed switch
141/142/143. Low/Medium/High Dehumidifier 4 - Low, medium, and high speed switch
145/146/147. Low/Medium/High Dehumidifier 5 - Low, medium, and high speed switch
149/150/151. Low/Medium/High Dehumidifier 6 - Low, medium, and high speed switch
153/154/155. Low/Medium/High Dehumidifier 7 - Low, medium, and high speed switch
157/158/159. Low/Medium/High Dehumidifier 8 - Low, medium, and high speed switch
PHOTO TBD
AVAILABLE ANALOGUE OUTPUT
...
From 10 to 16 are the same for dehumidifiers 2 to 8.
PHOTO TBD