Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Introduction

Each zone can send two types of requests to Dehumidifiers:

...

The Dehumidifier subsystem can be associated with a manifold/circuit; if associated, the circuit is activated when the valve control and at least one between dehumidification and integration control is active.

Note

  • If also or only the integration control is active, the circuit is activated in COMFORT mode.

  • if only the dehumidification control is active, the circuit is activated in ECONOMY mode.

...

  • 96. Dehumidifier 1 - switching dehumidification demand on and off

  • 100. Dehumidifier 2 - switching dehumidification demand on and off

  • 104. Dehumidifier 3 - switching dehumidification demand on and off

  • 108. Dehumidifier 4 - switching dehumidification demand on and off

  • 112. Dehumidifier 5 - switching dehumidification demand on and off

  • 116. Dehumidifier 6 - switching dehumidification demand on and off

  • 120. Dehumidifier 7 - switching dehumidification demand on and off

  • 124. Dehumidifier 8 - switching dehumidification demand on and off

  • 160. Integration 1 - switching integration demand on and off

  • 161. Integration 2 - switching integration demand on and off

  • 162. Integration 3 - switching integration demand on and off

  • 163. Integration 4 - switching integration demand on and off

  • 164. Integration 5 - switching integration demand on and off

  • 165. Integration 6 - switching integration demand on and off

  • 166. Integration 7 - switching integration demand on and off

  • 167. Integration 8 - switching integration demand on and off

  • 97. Valve 1 - switching the valve on and off

  • 101. Valve 2 - switching the valve on and off

  • 105. Valve 3 - switching the valve on and off

  • 109. Valve 4 - switching the valve on and off

  • 113. Valve 5 - switching the valve on and off

  • 117. Valve 6 - switching the valve on and off

  • 121. Valve 7 - switching the valve on and off

  • 125. Valve 8 - switching the valve on and off

  • 129/130/131. Low/Medium/High Dehumidifier 1 - Low, medium, and high speed switch

  • 133/134/135. Low/Medium/High Dehumidifier 2 - Low, medium, and high speed switch

  • 137/138/139. Low/Medium/High Dehumidifier 3 - Low, medium, and high speed switch

  • 141/142/143. Low/Medium/High Dehumidifier 4 - Low, medium, and high speed switch

  • 145/146/147. Low/Medium/High Dehumidifier 5 - Low, medium, and high speed switch

  • 149/150/151. Low/Medium/High Dehumidifier 6 - Low, medium, and high speed switch

  • 153/154/155. Low/Medium/High Dehumidifier 7 - Low, medium, and high speed switch

  • 157/158/159. Low/Medium/High Dehumidifier 8 - Low, medium, and high speed switch

...

AVAILABLE ANALOGUE OUTPUT

...

From 10 to 16 are the same for dehumidifiers 2 to 8.

PHOTO TBD