Introduction
Each zone can send two types of requests to Dehumidifiers:
...
The Dehumidifier subsystem can also manage three digital outputs and/or a 0/10 output for fan speed control: the output is activated together with the integration contact, and can take 3 values corresponding to low, medium, and high speed: among all the integration requests from various zones (each of which specifies if it wants a low, medium, or high integration see INTEGRATION OFFSET) the subsystem determines the highest request and applies it to the output (digital or analogue).
PHOTO TBD
The voltage levels corresponding to the 3 speeds can be set freely, and independently for each Dehumidifier; when the integration contact is switched-off, the output switches to 0 V and all digital outputs are open.
...
The Dehumidifier subsystem can be associated with a manifold/circuit; if associated, the circuit is activated when the valve control and at least one between dehumidification and integration control is active.
Note
If also or only the integration control is active, the circuit is activated in COMFORT mode.
if only the dehumidification control is active, the circuit is activated in ECONOMY mode.
Finally, both the dehumidifier and integration can activate a father dehumidifier and/or father integration, which will be activated at the same time:
PHOTO TBD
In Actual Status (bottom right of the page) it is possible to see the active functions.
USCITE DIGITALI DISPONIBILI
...
AVAILABLE DIGITAL OUTPUTS
The digital output available for Dehumidifiers are:
96. Deumidificatore Dehumidifier 1 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
100. Deumidificatore Dehumidifier 2 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
104. Deumidificatore Dehumidifier 3 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
108. Deumidificatore Dehumidifier 4 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
112. Deumidificatore Dehumidifier 5 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
116. Deumidificatore Dehumidifier 6 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
120. Deumidificatore Dehumidifier 7 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
124. Deumidificatore Dehumidifier 8 - accensione e spegnimento della richiesta di deumidificazioneswitching dehumidification demand on and off
160. Integrazione Integration 1 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
161. Integrazione Integration 2 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
162. Integrazione Integration 3 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
163. Integrazione Integration 4 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
164. Integrazione Integration 5 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
165. Integrazione Integration 6 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
166. Integrazione Integration 7 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
167. Integrazione Integration 8 - accensione e spegnimento della richiesta di integrazioneswitching integration demand on and off
97. Valvola Valve 1 - accensione e spegnimento della valvolaswitching the valve on and off
101. Valvola Valve 2 - accensione e spegnimento della valvolaswitching the valve on and off
105. Valvola Valve 3 - accensione e spegnimento della valvolaswitching the valve on and off
109. Valvola Valve 4 - accensione e spegnimento della valvolaswitching the valve on and off
113. Valvola Valve 5 - accensione e spegnimento della valvolaswitching the valve on and off
117. Valvola Valve 6 - accensione e spegnimento della valvolaswitching the valve on and off
121. Valvola Valve 7 - accensione e spegnimento della valvolaswitching the valve on and off
125. Valvola Valve 8 - accensione e spegnimento della valvolaswitching the valve on and off
129/130/131. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 1 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
133/134/135. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 2 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
137/138/139. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 3 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
141/142/143. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 4 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
145/146/147. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 5 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
149/150/151. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 6 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
153/154/155. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 7 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
157/158/159. BassaLow/MediaMedium/Alta Deumidificatore High Dehumidifier 8 - Consenso Velocità bassa, media e altaLow, medium, and high speed switch
PHOTO TBD
USCITE ANALOGICHE DISPONIBILI
...
AVAILABLE ANALOGUE OUTPUT
The analogue output available for each Dehumidifier is:
9. Deumidificatore 1 - corrisponde alla velocità del ventilatore
...
Dehumidifier 1 – corresponds to the fan speed
From 10 to 16 are the same for dehumidifiers 2 to 8.
PHOTO TBD