Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

To use this function, it is necessary at least to have installed firmware version 4.29 on the REG-DIN-8 and to use a RegConfig version 4.29 or later.

...

  1. Enter Configuration/2 and set the activation offset for the Integration function

PHOTO TBD

  1. Go to the Zones page and create the desired zones (in the example, 3 zones have been created) by associating a room probe or sensor. Then, in the Integration column, choose the sum referring to one of the 4 available dehumidifiers (∑D1, ∑D2, ∑D3, ∑D4), in the example the first has been chosen:

PHOTO TBD

  1. If the zones are served by the same duct unit, associate each zone with the same dehumidifier. In the example below, the first is associated with all zones:

PHOTO TBD

  1. Still remaining in the Zones page, enter Configuration Zone/2 and enter a value from 0 to 100 in the box indicated according to the weight of the individual room:

PHOTO TBD5. Spostarsi nella pagina Deumidificatori (D1) impostare il comando Integrazione su “Attivo se richiesto” in estate e/o in inverno in base alle necessità dell’impianto. Per quanto riguarda le impostazioni delle portate d’aria la velocità media viene ignorata:

  • la velocità bassa diventa la minima

  • la velocita alta diventa la massima

La velocità attuale dell’uscita 0/10V è la somma delle portate delle singole zone che fanno riferimento al deumidificatore 1, nell’esempio riportato 15+15+30 = 60, quindi 6 V.

Se la somma fosse inferiore a 30 o superiore a 90, l’uscita 0/10V sarebbe limitata a 3 V o 9 V.

 

  1. Move to the Dehumidifiers (D1) page and set the Integration control to “Active if

...

  1. requested” in summer and/or winter according to the needs of the system. Concerning Air Flows settings, the medium speed is ignored: 

...

  • Low speed becomes the minimum

...

  • High speed becomes the maximum

The current speed of the 0/10V output is the sum of the flow of the individual zones that refer to the dehumidifier 1, in the example above 15+15+30 = 60, therefore 6V.

If the sum were less than 30 0r or greater than 90, the 0/10V would be limited to 3 V or 9 V.

PHOTO TBD