  1. Entrare in Configurazione 2 e impostare gli offset desiderati per l’attivazione della funzione integrazione

To use this function, it is necessary at least to have installed firmware version 4.29 on the REG-DIN-8 and to use a RegConfig version 4.29 or later.

This logic was created with the aim to manage a single channelled unit with several channels that integrate different rooms in cooling and/or heating. It is required that the demands of the individual room (opening of the dampers) are summed up and transferred via 0/10V to the unit’s fan, that will increase its speed as the dampers open, that is as the rooms are in call.

Below are the various points for the correct use of this function:

  1. Enter Configuration/2 and set the activation offset for the Integration function

...

2. Andare nella pagina Zone e creare le zone desiderate (nell’esempio sotto sono state create 3 zone) associando una sonda o un sensore ambiente. Poi nella colonna Integrazione scegliere la sommatori riferita ad uno dei 4 deumidificatori disponibili (∑D1, ∑D2, ∑D3, ∑D4), nell’esempio si sceglie il primo:

 

  1. Go to the Zones page and create the desired zones (in the example, 3 zones have been created) by associating a probe or a room sensor. Then, in the Integration column, choose the summation referring to one of the 4 available dehumidifiers (∑D1, ∑D2, ∑D3, ∑D4), in the example the first has been chosen:

...

3. Se le zone sono servite dalla stessa unità canalizzata associare a ciascuna zona lo stesso deumidificatore, nell’esempio riportato si associa a tutte le zone il primo:

 

  1. If the zones are served by the same channelled unit, associate each zone with the same dehumidifier. In the example below, the first is associated with all zones:

...

4. Sempre rimanendo nella pagina Zone entrare in Configurazione Zona/2 e inserire un valore da 0 a 100 sulla casella indicata in base al peso delle singole stanze:

 

  1. Still remaining on the Zones page, enter Configuration Zone/2 and enter a value from 0 to 100 on the box indicated according to the weight of the individual room:

Image Modified

5. Spostarsi nella pagina Deumidificatori (D1) impostare il comando Integrazione su “Attivo se richiesto” in estate e/o in inverno in base alle necessità dell’impianto. Per quanto riguarda le impostazioni delle portate d’aria la velocità media viene ignorata:

...

Se la somma fosse inferiore a 30 o superiore a 90, l’uscita 0/10V sarebbe limitata a 3 V o 9 V.

 

  1. Move to the Dehumidifiers (D1) page and set the Integration control to “Active if requested) in summer and/or winter according to the needs of the system. Concerning Air Flows settings, the medium speed is ignored: 

·        Low speed becomes the minimum

·        High speed becomes the maximum

The current speed of the 0/10V output is the sum of the flow of the individual zones that refer to the dehumidifier 1, in the example above 15+15+30 = 60, therefore 6V.

If the sum were less than 30 0r greater than 90, the 0/10V would be limited to 3 V or 9 V.

Image Modified