Associated Sensor
Normally a temperature (or temperature and humidity) sensor is associated to a zone via the Sensor parameter on the Configuration Zone/1 sub page:
...
The Temperature and Humidity value of the selected sensor can be visualized on the left of the Zone page.
Note
Remember that a zone can also operate without associated sensor; in this case, when the zone is active (in Comfort, Economy, or Antifreeze Active mode), the corresponding output will be always active. Some possible uses of this configuration are:
...
Each individual zone can be associated with a temperature value correction, that is an Offset value that will be added (or subtracted, if negative) to the value detected by the temperature probe. This value is set in the Configuration Zone/2:PHOTO TBD
...
Temperature and Room Humidity Set Point
...
Summer Comfort Set: used if the set season is Summer and the working mode is Comfort.
Summer Economy Set: used if the set season is Summer and the working mode is Economy.
Winter Comfort Set: used if the set season is Winter and the working mode is Comfort.
Winter Economy Set: used if the set season is Winter and the working mode is Economy.
Humidity Set: used in both seasons, either in Economy or Comfort
PHOTO TBD
The current set temperature is on the left side of the Zone Page.
Note
From version 4.30 of the REG Firmware, a new Function is available, which also allows you to manage a humidity economy set point (see ECONOMY FUNCTION FOR THE DEHUMIDIFIERS).
...
Limits are set on Configuration 1 page:
PHOTO TBD
Warning
If RegConfig is used, these limits are bypassed, while they can’t be bypassed by REG-TFT and REG-DOT-B display and by REG-THL-SXX sensors
...
Temperature and Humidity hysteresis are also set equal for all the zones in Configuration 1:
PHOTO TBD
So, if the set point of a zone is 21°C, the zone will activate below 21°C and will deactivate above 21,3°C in heating. If the humidity set point is 55%, the zone (if it has a humidity sensor) will activate the dehumidification request above 55% and deactivate it below 50%.
...