Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Introduction

The REG System is specifically designed for radiant cooling system and provides some algorithms to prevent condensation from forming on the radiant surface during summer operation.

  1. The system calculates the Dew Point Temperature (Dew Point) for each zone equipped with a temperature+humidity sensor, that is the critical temperature below which condensation forms under the zone’s current conditions.

  2. The Dew Point Temperature, corrected by an offset that can be set differently from zone to zone (Dew Point Control parameter, indicated as Ctrl DP in the Configuration Zone/1 sub page), is compared with the Outlet temperature of the circuit serving the zone; if the water temperature is equal or below the calculated limit, there are the conditions for condensation formation.

  3. If the circuit serving the zone is equipped with a mixed valve controlled by the REG System, the Outlet temperature of the circuit is increased if the water temperature is too close to the Dew Point Temperature, otherwise the zone will be blocked.

Note

For zones used as “Integration” to the dehumidifiers in Cooling system, the Dew Point Control (Ctrl DP) value must be set very high (in the order of 20°C), because the associated user does not act directly on the radiant surface, but it is a “Support” to the action of the dehumidifier.

...

  • Screed thickness

  • Materials used for floor construction

  • Radiant system pipes materials

Note

Within the Zone section (in the red frame), for each zone equipped with humidity and temperature sensor, the Dew Point (°C), indicated by the abbreviation DP in the green frame, is calculated:

PHOTO TBD

for the zones without humidity sensor, the DP is NC, not calculated.

The calculated DP must be compared with the floor surface temperature, which is the sum of the cold-water temperature and of a delta that take into consideration the type of covering. The parameter that allows the delta to be taken into account is the Dew Point Control (K, Kelvin degrees are used to indicate that the parameter is a temperature difference and not a temperature value), indicated by the abbreviation Ctrl DP in the green frame:

PHOTO TBD

Let us, for example, consider the zone 6, for which the calculated dew point is 15°C and the Dew Point control is equal to 3 K. The calculated dew point (15°C) will not be compared to the value read by the circuit water outlet temperature associated with the zone (C2), but with the value read by the probe of C2 + 3 K. The zone 6 will be blocked to prevent condensation if the water outlet temperature of the associated C2 circuit is less then 12°C (15°C - 3 K). While zone 7 will be blocked if the water outlet temperature of the associated C2 circuit drops below 10,3°C (13,3°C - 3 K).

...

  • If 0 is indicated, it means that the room temperature is not considered in the calculation and that simply the DP is compared with the water outlet temperature + delta K of the Ctrl DP box;

  • If 100 is indicated, it means that water temperature is not considered in the calculation and that the DP is compared with the room temperature of the zone;

  • If a value between 1 a 99 is indicated, then a weighted average of the two temperatures is calculated to find the reference temperature to compare with DP. For example: I use 50, this means that the temperature to be compared with DP is = [(room T * 50) + (Outlet T + delta K) * 50]/100

2. Controllo della Temperatura di Mandata

Prima di mettere in pratica il blocco della zona il sistema REG prova ad aumentare la temperatura dell’acqua chiudendo la valvola miscelatrice o aumentando il set point al chiller (mediante 0/10V, Opentherm o Modbus).

Per fare ciò il sistema REG utilizza il parametro Offset PdR / T Mand, evidenziato in giallo nella pagina Configurazione 1, è un aumento dato alla temperatura di mandata di tutti i circuiti per evitare di stare troppo vicino al Punto di Rugiada calcolato. Questa logica evita ripetuti blocchi e sblocchi delle zone in quanto protegge dalla condensa alzando la temperatura di mandata dell’acqua, prima che intervenga il blocco della zona.

...

Water Outlet Temperature Control

Before blocking the zone, the REG System tries to increase the water temperature by closing the mixing valve or by increasing the set point at the chiller (via 0/10V, OpenTherm, or Modbus).

To do this, the REG System uses the parameter Offset DP/Water Outlet T, highlighted in yellow in the Configuration/1 page; it is an increase given to the water Outlet temperature of all circuits to avoid being too close to the calculated Dew Point. This logic avoids the repeated lockout and unlocking of the zones as it protects against condensation by raising the water outlet temperature, before the zone block intervenes.

...

Considerando ad esempio di usare 3 K come Offset PdR / Mandata e avendo una zona collegata al circuito 1 che è a rischio condensa se la temperatura di mandata < 6,8°C (PdR calcolato = 7,3°C e CtrlPdR = 0,5 k con 0 = non si considera la temperatura ambiente), si può notare che il limite inferiore di mandata è 6,8°C + 3 = 9,8 °C che corrisponde anche al set point (temperatura desiderata) > 5 °C che sarebbe il set point del circuito in freddo in modalità Comfort:

...