Introduction

...

  1. The system calculates the Dew Point Temperature (Dew Point) for each zone equipped with a temperature+humidity sensor, that is the critical temperature below which condensation forms under the zone’s current conditions.

  2. The Dew Point Temperature, corrected by an offset that can be set differently from zone to zone (Dew Point Control parameter, indicated as Ctrl DP in the Configuration Zone/1 sub page), is compared with the Outlet temperature of the circuit serving the zone; if the water temperature is equal or below the calculated limit, there are the conditions for condensation formation.

  3. If the circuit serving the zone is equipped with a mixed valve controlled by the REG System, the Outlet temperature of the circuit is increased if the water temperature is too close to the Dew Point Temperature, otherwise the zone will be blocked.

Note

Per le zone utilizzate come "Integrazione" al deumidificatore negli impianti di Raffrescamento, il valore del Controllo del Punto di Rugiada (Ctrl PdR) deve essere settato molto alto (nell'ordine di 20 °C) in quanto l'utenza ad essi associata non agisce direttamente sulla superficie radiante, ma è un "Supporto" all'azione del deumidificatore.

Controllo della Temperatura e Blocco della Zona

Il sistema REG è in grado di gestire in maniera intelligente e flessibile la condensa in due modi principali:

  • Controllo della Temperatura di Mandata

  • Blocco della Zona

Entrambi i controlli necessitano dell’installazione di una sonda di mandata per il controllo della temperatura dell’acqua dei circuiti / collettori, mentre il Controllo della temperatura di mandata necessita della presenza di una valvola miscelatrice oppure di poter inviare direttamente alla sorgente di acqua fredda il set point (mediante 0/10V, Modbus o OpenTherm).

Nel caso in cui non ci sia collegata una sonda di mandata dell’acqua nel momento in cui il sistema deve confrontare il risultato del calcolo del punto di rugiada userà il valore indicato in configurazione 1 “Limite Punto di Rugiada Teorico”:

...

ovviamente si sconsiglia di utilizzare questo modo di gestione della condensaFor zones used as “Integration” to the dehumidifiers in Cooling system, the Dew Point Control (Ctrl DP) value must be set very high (in the order of 20°C), because the associated user does not act directly on the radiant surface, but it is a “Support” to the action of the dehumidifier.

Temperature Control and Zone Locking

The REG System is able to manage, in a smart and flexible way, the condensation in two main ways:

  • Circuit Water Outlet Temperature Control

  • Zone Block

Both controls require the installation of a water probe to control the water temperature of the circuits/manifolds, while the water outlet temperature Control required the presence of a mixing valve or the ability to send the set point directly to the cold-water source (via 0/10V, Modbus, or OpenTherm). 

If there is no water outlet probe connected when the system needs to compare the result of the dew point calculation, it will use the value indicated in configuration/1 “Theoric Dew Point Limit”:

...

 It is obviously not recommended to use this mode of dew point management.

1. Calcolo della Temperatura Superficiale

...

  • Spessore dei massetti

  • Materiali utilizzati per la costruzione del pavimento

  • Materiale da cui sono composti i tubi dell'impianto radiante

Nota

All'interno della sezione Zone (nel riquadro rosso) viene calcolato per ogni zona dotata di sensore di temperatura e di umidità il Punto di Rugiada (°C) indicato dalla sigla PdR nel riquadro verde:

...