Associated Sensor
Normally a temperature (or temperature and humidity) sensor is associated to a zone via the Sensor parameter on the Configuration Zone/1 sub page:
...
The Temperature and Humidity value of the selected sensor can be visualized on the left of the Zone page.
Note
Remember that a zone can also operate without associated sensor; in this case, when the zone is active (in Comfort, Economy, or Antifreeze Active mode), the corresponding output will be always active. Some possible uses of this configuration are:
...
The current set temperature is on the left side of the Zone Page.
Note
From version 4.30 of the REG Firmware, a new Function is available, which also allows you to manage a humidity economy set point (see ECONOMY FUNCTION FOR THE DEHUMIDIFIERS).
...
Limits are set on Configuration 1 page:
PHOTO TBD
Warning
If RegConfig is used, these limits are bypassed, while they can’t be bypassed by REG-TFT and REG-DOT-B display and by REG-THL-SXX sensors
...
Temperature and Humidity hysteresis are also set equal for all the zones in Configuration 1:
PHOTO TBD
So, if the set point of a zone is 21°C, the zone will activate below 21°C and will deactivate above 21,3°C in heating. If the humidity set point is 55%, the zone (if it has a humidity sensor) will activate the dehumidification request above 55% and deactivate it below 50%.
...