To use this function, it is necessary at least to have installed firmware version 4.29 on the REG-DIN-8 and to use a RegConfig version 4.29 or later.

...

  1. Enter Configuration/2 and set the activation offset for the Integration function

...

  1. Go to the Zones page and create the desired zones (in the example, 3 zones have been created) by associating a room probe or sensor. Then, in the Integration column, choose the sum referring to one of the 4 available dehumidifiers (∑D1, ∑D2, ∑D3, ∑D4), in the example the first has been chosen:

PHOTO TBD

  1. If the zones are served by the same duct unit, associate each zone with the same dehumidifier. In the example below, the first is associated with all zones:

PHOTO TBD

  1. Still remaining in the Zones page, enter Configuration Zone/2 and enter a value from 0 to 100 in the box indicated according to the weight of the individual room:

PHOTO TBD

  1. Move to the Dehumidifiers (D1) page and set the Integration control to “Active if requested” in summer and/or winter according to the needs of the system. Concerning Air Flows settings, the medium speed is ignored: 

...

If the sum were less than 30 or greater than 90, the 0/10V would be limited to 3 V or 9 V.

PHOTO TBD