To use this function, it is necessary at least to have installed firmware version 4.29 on the REG-DIN-8 and to use a RegConfig version 4.29 or later.

...

  1. Enter Configuration/2 and set the activation offset for the Integration function

PHOTO TBD

  1. Go to the Zones page and create the desired zones (in the example, 3 zones have been created) by associating a room probe or sensor. Then, in the Integration column, choose the sum referring to one of the 4 available dehumidifiers (∑D1, ∑D2, ∑D3, ∑D4), in the example the first has been chosen:

PHOTO TBD

  1. If the zones are served by the same duct unit, associate each zone with the same dehumidifier. In the example below, the first is associated with all zones:

...

4. Sempre rimanendo nella pagina Zone entrare in Configurazione Zona/2 e inserire un valore da 0 a 100 sulla casella indicata in base al peso delle singole stanze:

 

...

PHOTO TBD

  1. Still remaining in the Zones page, enter Configuration Zone/2 and enter a value from 0 to 100

...

  1. in the box indicated according to the weight of the individual room:

Image RemovedPHOTO TBD

5. Spostarsi nella pagina Deumidificatori (D1) impostare il comando Integrazione su “Attivo se richiesto” in estate e/o in inverno in base alle necessità dell’impianto. Per quanto riguarda le impostazioni delle portate d’aria la velocità media viene ignorata:

...

If the sum were less than 30 0r greater than 90, the 0/10V would be limited to 3 V or 9 V.

Image RemovedPHOTO TBD