To use this function, it is necessary at least to have installed firmware version 4.29 on the REG-DIN-8 and to use a RegConfig version 4.29 or later.

...

  1. Go to the Zones page and create the desired zones (in the example, 3 zones have been created) by associating a room probe or sensor. Then, in the Integration column, choose the sum referring to one of the 4 available dehumidifiers (∑D1, ∑D2, ∑D3, ∑D4), in the example the first has been chosen:

...

  1. If the zones are served by the same duct unit, associate each zone with the same dehumidifier. In the example below, the first is associated with all zones:

PHOTO TBD

  1. Still remaining in the Zones page, enter Configuration Zone/2 and enter a value from 0 to 100 in the box indicated according to the weight of the individual room:

PHOTO TBD

  1. Move to the Dehumidifiers (D1) page and set the Integration control to “Active if requested” in summer and/or winter according to the needs of the system. Concerning Air Flows settings, the medium speed is ignored: 

...

If the sum were less than 30 or greater than 90, the 0/10V would be limited to 3 V or 9 V.

PHOTO TBD