Zones are the basic element of the REG System and it can manage a maximum of 32 zones. Without Zone, Dehumidifiers, Circuits, and consequently Source cannot be activated.
...
A Circuit, when the zone is activated to heat and/or cool.
A Dehumidifier, when the zone detects that dehumidification is required.
Another Dehumidifier (which in most cases is the same as the previous point), when the zone detects that it is necessary to integrate the heating/cooling function.
PHOTO TBD
Note
In a radiant system, each room of the system equipped with a sensor (temperature or temperature + humidity) is managed by a Zone.
...
In a bathroom, the same sensor can control both the radiant floor and a towel heater; in this case, we should configure TWO zones, which use the same sensor.
PHOTO TBD
In a mixed system, the same sensor can control the radiant floor in winter and a fan coil in summer; even in this case we should configure TWO zones, which are based on the same sensor.
A zone could NOT be associated with any sensor, for example:
In a bathroom the towel heater may be switched on at certain times, regardless of the sensor reading in the room.
A zone could be used to control the change of air: even in this case the switching on could be timed and not take any sensor into account (see CMV FUNCTION WITH TIMETABLE AND/OR VOC SENSOR).
Utilizzo delle Zone in impianti per il controllo di circuiti Diretti/Miscelati
Negli impianti utilizzati per il controllo dei Circuiti Diretti/Miscelati, le Zone assumono un significato leggermente diverso rispetto a quello canonico in quanto qua le zone non sono degli Ambienti/Locali, ma assumono a tutti gli effetti il significato di Circuiti. Nel seguito
Le Zone sono associate ai Circuiti Diretti/Miscelati
I Sensori di Zona generalmente non vengono utilizzati
Nel seguito verrà riportato un esempio illustrativo:
Caso tipico: Controllo di 1 Circuito Diretto e 2 Miscelati
L'impianto in questione controlla il funzionamento di una centrale termica e in particolare sono presenti tre circuiti:
Il circuito 3 è di tipo Diretto con temperatura di mandata a 60 °C
I circuiti 1 e 2 sono di tipo Miscelato per il controllo del riscaldamento di superfici radianti, con temperatura di mandata fissata rispettivamente a 24 °C e 20 °C.
In questo caso la logica con cui dovrà essere costruito l'impianto è la seguente:
...
Devono essere impostate 3 Zone, ognuna corrispondente ad un circuito.
...
Ad ogni zona va associato un Circuito, su ognuno dei quali deve essere presente un sensore per il controllo della Temperatura di mandata (vedere SET POINT AND SENSORS SETTINGS dei Circuiti).
...
Per quanto riguarda l'attivazione delle zone (o meglio, dei circuiti), associare ad ognuna di esse un proprio orologio per determinare lo stato di funzionamento e non impostare sensori di zona, in modo tale che se l'orologio è attivo, la zona corrispondente è automaticamente attiva.
...
E' possibile associate un segnale di attivazione/abilitazione (classico Termostato ambiente)
...
Associare al circuito diretto il funzionamento di 1 Pompa di rilancio.
...
Use of the zones in system for the control of Direct/Mixed circuits
In the system used for the control of Direct/Mixed circuits, the Zones take on a slightly different meaning from the standard one, as here the zones are not Environments/Locations, but to all intents and purposes take on the meaning of Circuits. In the following:
Zones are associated with Direct/Mixed Circuits
Zone Sensors are generally not used
An example is given below:
Typical case: Control of 1 Direct and 2 Mixed Circuits
The system controls the operation of a central thermic system and in particular there are three circuits:
Circuit 3 is of the Direct type with flow temperature set at 60 °C
Circuits 1 and 2 are of the Mixed type to control the heating of radiant surfaces, with flow temperature set at 24°C and 20°C respectively.
In this case the logic with which the system must be constructed is as follow:
3 Zones must be set up, each corresponding to a circuit.
A Circuit must be associated with each zone, every circuit must have a sensor to control the Flow Temperature (see SET POINT AND SENSORS SETTINGS of the Circuits).
As regards the activation of the zones (or rather, circuits), associate each one with its own timetable to determine the operating status and do not set zone sensor, so that if the timetable is active, the corresponding zone is automatically active.
It is possible to associate an activation/enabling signal (classic room Thermostat)
Associate to the direct circuit the operation of 1 water pump.
Associate to each one of mixed circuit the control of 1 water pump and 1 mixing valve (see WATER PUMPS AND MIXING VALVES SETTINGS)
...
PHOTO TBD
Descrizione Zona
Ad ogni Zona è assegnata una Descrizione (vedere DESCRIPTIONS), cioè un breve testo (massimo 16 caratteri) che permetta di identificare agevolmente la funzione della Zona, impostabile nella Pagina Zone - Configurazione Zona /1.
...
Le zone senza descrizione non sono visualizzate neanche in telegestione!
Attenzione
Su impianti molto complessi non associare descrizioni alle Zone potrebbe essere fonte di fraintendimenti e complicazioni durante l’assistenze. Quindi sempre meglio assegnare un nome.
...