OBJECTIVE

...

The following image shows, within the OpenTherm page of the RegConfig, the position of the System Cascade control Algorithm section (red) and the Buffer tank Compensation Temperature section (blue), closely related to the PID cascade algorithm:

PHOTO TBD

The cascade algorithm can be of three types:

...

Enabled OpenTherm generators are those generators that have a number (which can range from 1, highest priority, to 8, lowest priority) in the Generators section (highlighted in green) on the OpenTherm page and not OFF in the box corresponding to the “Heat/Cool” column. The number indicates the priority of the call, so in the image below G1 and G3 generators have priority 1 (they are called first), while G2 has priority 2 and G4 priority 3:

...

Warning

Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.

...

Attention: the powers are expressed in percentage, so if generators of different power are present, for example 24 kW and 35 kW, the same % power corresponds to a different real power. Moreover, some boilers give the real power output, so they consider 0% with boiler off, while with the flame on the power value read by the system is ≥ 15-17%, that is the minimum power at which they can modulate; other boilers instead indicate the % in relation to the useful regulation range, so with 0% they indicate that the boiler is working at the minimum of its modulation (probably 15-20% of the power rating), but still on. This may have an impact on the setting (although usually not a big one): for the former the minimum power = 30% probably indicates an actual 30%, while in the latter case the minimum power = 30% probably indicates roughly an actual 40% value, assuming its minimum is 15%, this would be [(100%-15%)*0,3+15%)];

  • Idle: questo parametro (che significa inattivo) è il limite inferiore della limitazione di potenza, un generatore non viene mai limitato ad una potenza inferiore a Idle. Quindi se la potenza minima erogata tra i generatori accesi è 5% e Gap é 8%, la Potenza massima sarebbe 13%, ma se Idle è 30% allora i generatori saranno limitati a 30%. Questo parametro è fondamentale nel momento in cui un nuovo generatore viene acceso. Ipotizziamo di aver acceso 2 generatori che sono intorno al 45 % di potenza entrambi. La potenza minima erogata tra i due generatori supera il 50% (Pot Up) e il sistema ne chiama un terzo, il quale parte da potenza 0%. Se il parametro Gap è 8% significa che tra il generatore che esprime la potenza minima e quello che esprime la massima ci può essere una differenza al massimo dell’8%. Quindi se il terzo generatore è a 0%, gli altri dovrebbero stare a 8%! Per evitare ciò si mette un limite inferiore alla potenza dei generatori già attivi, ad esempio 30% (Idle). Quindi anche se i generatori accesi dovrebbero per rispettare il parametro Gap stare sull’8% di potenza andranno al valore di Idle impostato; this parameter (that means inactive) is the lower limit of the power limitation; a generator is never limited to a power lower than Idle. So, if the minimum power output between the switched-on generators is 5% and Gap is 8%, the maximum power would be 13%, but if Idle is 30%, then the generators will be limited at 30%. This parameter is essential when a new generator is switched on. Let us assume that we have switched on 2 generators that are both roughly 45% power. The minimum power output between the generators exceeds 50% (PotUp) and the system calls a third one, which starts at 0% power. If the Gap parameter is 8%, it means that between the generator expressing the minimum power and the one expressing the maximum power there can be a difference of at most 8%. So, if the third generator is at 0%, the others should be at 8%! To avoid this, a lower limit is put on the power of the already active generators, for example 30% (Idle). So, even if the generators that are switched on should stay at 8% power to conform to the Gap parameter, they will go to the set Idle value. 

GESTIONE DEI GENERATORI DEGRADATI

...

l risultato delle impostazioni effettuate è visualizzato nella parte in alto a destra della pagina OpenTherm “Stato Richiesta Generatori”:

PHOTO TBD

  • Abilita Set/Riscaldamento: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti non sta arrivando nessuna richiesta a OpenTherm.

  • Abilita Set/Sanitario: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto per la produzione di Acqua calda Sanitaria. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti o dalla pagina ACS non sta arrivando nessuna richiesta a OpenTherm.

  • Numero Generatori attivi (cascata): indica quanti generatori sono stati attivati per la cascata in riscaldamento (non per la produzione ACS).

  • l’ultimo rettangolo in basso (riquadro giallo) è il countdown della pausa tra variazioni in centesimi di secondo.

PHOTO TBD

Facendo sempre riferimento all'immagine relativa alla sezione Generatori della pagina OpenTherm:

PHOTO TBD

si fa presente quanto segue:

...

Nella parte inferiore della pagina OpenTherm si riporta per ogni generatore il risultato delle richieste di riscaldamento e ACS (riquadro rosso) e il feedback dai generatori verso il sistema REG (giallo):

PHOTO TBD

Evidenziato in rosso si trova:

...

A parità di priorità l’accensione segue l’ordine numerico dei generatori per la prima accensione, mentre per le successive accensioni i generatori vengono fatti ruotare:

PHOTO TBD

Quindi nell’esempio sopra riportato alla prima accensione l’ordine sarà:

...