Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

OBJECTIVE

...

The following image shows, within the OpenTherm page of the RegConfig, the position of the System Cascade control Algorithm section (red) and the Buffer tank Compensation Temperature section (blue), closely related to the PID cascade algorithm:

PHOTO TBD

The cascade algorithm can be of three types:

...

Enabled OpenTherm generators are those generators that have a number (which can range from 1, highest priority, to 8, lowest priority) in the Generators section (highlighted in green) on the OpenTherm page and not OFF in the box corresponding to the “Heat/Cool” column. The number indicates the priority of the call, so in the image below G1 and G3 generators have priority 1 (they are called first), while G2 has priority 2 and G4 priority 3:

...

Warning

Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.

...

  • Idle: this parameter (that means inactive) is the lower limit of the power limitation; a generator is never limited to a power lower than Idle. So, if the minimum power output between the switched-on generators is 5% and Gap is 8%, the maximum power would be 13%, but if Idle is 30%, then the generators will be limited at 30%. This parameter is essential when a new generator is switched on. Let us assume that we have switched on 2 generators that are both roughly 45% power. The minimum power output between the generators exceeds 50% (PotUp) and the system calls a third one, which starts at 0% power. If the Gap parameter is 8%, it means that between the generator expressing the minimum power and the one expressing the maximum power there can be a difference of at most 8%. So, if the third generator is at 0%, the others should be at 8%! To avoid this, a lower limit is put on the power of the already active generators, for example 30% (Idle). So, even if the generators that are switched on should stay at 8% power to conform to the Gap parameter, they will go to the set Idle value. 

GESTIONE DEI GENERATORI DEGRADATI

Restano da impostare 2 parametri (non obbligatori)MANAGEMENT OF DEGRADED GENERATORS

Two (non-mandatory) parameters are left to be set:

  • Power degraded

  • Temperatura Temperature degraded

se lasciati a zero l’algoritmo non gestisce i generatori degradati.

Un generatore viene considerato degradato se:

...

è passato il tempo di pausa (cioè non si considerano le condizioni durante l’intervallo successivo all’aggiunta/rimozione di una caldaia);

...

un generatore è in richiesta di riscaldamento o raffrescamento (non si considera la produzione ACS);

...

la potenza a cui è limitato il generatore è maggiore della potenza degradata

...

la temperatura di mandata del generatore è inferiore al set richiesto al generatore di più della Temperatura degradata (T mandata < set point - temperatura degradata dove quest’ultima è un delta di temperatura K e non un valore assoluto). Ad esempio se il set point è 40°C e la temperatura degradata 5 K, la temperatura del generatore deve scendere sotto i 35°C prima di poter essere degradato sempre che si verifichino anche gli altri quattro punti;

...

If left at zero, the algorithm does not manage degraded generators.

A generator is considered degraded if:

  1. The stop time is passed (that is the conditions during the pause following the addition/removal of a boiler are not considered);

  2. A generator is in heating or cooling demand (the DHW production is not considered);

  3. The power to which the generator is limited is bigger than the power degraded.

  4. The generator water outlet temperature is lower than the set point required of the generator less the temperature degraded (T water outlet < set point – temperature degraded, where the latter is a temperature delta K and not an absolute value). For example, if the set point is 40°C and the degraded temperature is 5 K, the generator temperature must drop below 35°C before it can be degraded, as long as the other four points also occur;

  5. The generator power output is lower that the “Power degraded” (which is an absolute power and not a power delta). For example, if the power degraded is 20%, the power output of the generator must drop below 20% before it can be degraded, as long as the other four points also occur.

Se un generatore viene degradato il sistema lo esclude da tutti i calcoli illustrati (calcolo potenza minima, potenza massima per confronto con PotUp, PotDown, Gap e Idle).

l risultato delle impostazioni effettuate è visualizzato nella parte in alto a destra della pagina OpenTherm “Stato Richiesta Generatori”:

PHOTO TBD

  • Abilita Set/Riscaldamento: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti non sta arrivando nessuna richiesta a OpenTherm.

  • Abilita Set/Sanitario: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto per la produzione di Acqua calda Sanitaria. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti o dalla pagina ACS non sta arrivando nessuna richiesta a OpenTherm.

  • Numero Generatori attivi (cascata): indica quanti generatori sono stati attivati per la cascata in riscaldamento (non per la produzione ACS).

  • l’ultimo rettangolo in basso (riquadro giallo) è il countdown della pausa tra variazioni in centesimi di secondo.

PHOTO TBD

Facendo sempre riferimento all'immagine relativa alla sezione Generatori della pagina OpenTherm:

PHOTO TBD

si fa presente quanto segue:

...

Nella parte inferiore della pagina OpenTherm si riporta per ogni generatore il risultato delle richieste di riscaldamento e ACS (riquadro rosso) e il feedback dai generatori verso il sistema REG (giallo):

PHOTO TBD

Evidenziato in rosso si trova:

...

A parità di priorità l’accensione segue l’ordine numerico dei generatori per la prima accensione, mentre per le successive accensioni i generatori vengono fatti ruotare:

PHOTO TBD

Quindi nell’esempio sopra riportato alla prima accensione l’ordine sarà:

...