OBJECTIVE
...
The following image shows, within the OpenTherm page of the RegConfig, the position of the System Cascade control Algorithm section (red) and the Buffer tank Compensation Temperature section (blue), closely related to the PID cascade algorithm:
PHOTO TBD
The cascade algorithm can be of three types:
...
Enabled OpenTherm generators are those generators that have a number (which can range from 1, highest priority, to 8, lowest priority) in the Generators section (highlighted in green) on the OpenTherm page and not OFF in the box corresponding to the “Heat/Cool” column. The number indicates the priority of the call, so in the image below G1 and G3 generators have priority 1 (they are called first), while G2 has priority 2 and G4 priority 3:
...
Warning
Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.
...
Stop between changes (s): the variation is the change corresponding to the switching on or off of an OpenTherm generator. The pause between two variations it the minimum time that passes between the switching on or off of an OpenTherm generator and its subsequent switching on (or subsequent switching off) of another OpenTherm generator. For example, if at time x a generator is switched on, for the time indicated in the Stop between changes box, the algorithm will not add or remove generators (even though the result of the calculation would require it) to give the switched-on generators time to get up to speed and see the effects on the system;
PotUp [%]: among all the switched-on boilers (with flame and heating on), ignoring those that maybe are degraded and those that are not producing DHW, the lowest power output value (in %) is compared with PotUp: if higher, another generator is switched on. Usually set at 50%. If only one generator is switched on, the only power output will be compared with PoutUp. It must not be forgotten that any limits given by the number of generators start/minimum/maximum must be always respected, so for example if there is a system with 8 generators enabled, but the maximum number of generators is 6, the system will call the various generators in rotation, but it will never switch on more than 6 generators at the same time even though the algorithm would require it;
PotDown [%]: among all the switched-on boilers (with flame and heating on), ignoring those that maybe are degraded and those that are not producing DHW, the lowest power output value (in%) is compared with PotDown: if lower, the first boiler that had been switched on is switched off. Usually set at 30%. If only one boiler is switched on, the only power output is compared with PotDown. Even in this case, the system can keep removing generators, but it will never drop below the start generator number, unless the heating demand from the zones stops;
Gap [%]: rappresenta l’escursione massima di potenza che ci può essere tra il generatore che lavora di meno e quella che lavora di più, di solito impostato a 8 %. Questo parametro serve per far lavorare i generatori accesi più o meno alla stessa potenza. Quindi se la potenza minima espressa tra i generatori accesi è 25% e Gap è 8%, tutti i generatori verranno limitati al 33% (= Potenza Massima). Attenzione: le potenze sono espresse in percentuale, quindi se ci sono generatori di potenza diversa, ad esempio da 24kW e 35kW, a parità di potenza % corrisponde una potenza effettiva diversa. Inoltre alcune caldaie danno in uscita la potenza effettiva, quindi considerano 0% con caldaia spenta, mentre con fiamma accesa il valore di potenza letto dal sistema è ≥ 15-17%, cioè la potenza minima a cui riescono a modulare; altre invece indicano la % rispetto al range utile di regolazione, quindi con 0% indicano che la caldaia sta lavorando al minimo della sua modulazione (probabilmente un 15-20% della potenza nominale), ma comunque accesa. Questo può avere un impatto sulle impostazioni (anche se di solito non grande): per le prime la potenza minima = 30% indica un 30% effettivo, mentre nel secondo caso la potenza minima = 30% indica probabilmente più un valore intorno al 40% effettivo, supponendo che il suo minimo sia il 15%, sarebbe represents the maximum power range that can be between the generator working less and the one working more, usually set at 8%. This parameter is useful to make the switched-on generators work at, more or less, the same power. So, if the minimum power expressed between the switched-on generators is 25% and Gap is 8%, all the generators are limited to 33% (=Maximum Power).
Attention: the powers are expressed in percentage, so if generators of different power are present, for example 24 kW and 35 kW, the same % power corresponds to a different real power. Moreover, some boilers give the real power output, so they consider 0% with boiler off, while with the flame on the power value read by the system is ≥ 15-17%, that is the minimum power at which they can modulate; other boilers instead indicate the % in relation to the useful regulation range, so with 0% they indicate that the boiler is working at the minimum of its modulation (probably 15-20% of the power rating), but still on. This may have an impact on the setting (although usually not a big one): for the former the minimum power = 30% probably indicates an actual 30%, while in the latter case the minimum power = 30% probably indicates roughly an actual 40% value, assuming its minimum is 15%, this would be [(100%-15%)*0,3+15%)];
Idle: questo parametro (che significa inattivo) è il limite inferiore della limitazione di potenza, un generatore non viene mai limitato ad una potenza inferiore a Idle. Quindi se la potenza minima erogata tra i generatori accesi è 5% e Gap é 8%, la Potenza massima sarebbe 13%, ma se Idle è 30% allora i generatori saranno limitati a 30%. Questo parametro è fondamentale nel momento in cui un nuovo generatore viene acceso. Ipotizziamo di aver acceso 2 generatori che sono intorno al 45 % di potenza entrambi. La potenza minima erogata tra i due generatori supera il 50% (Pot Up) e il sistema ne chiama un terzo, il quale parte da potenza 0%. Se il parametro Gap è 8% significa che tra il generatore che esprime la potenza minima e quello che esprime la massima ci può essere una differenza al massimo dell’8%. Quindi se il terzo generatore è a 0%, gli altri dovrebbero stare a 8%! Per evitare ciò si mette un limite inferiore alla potenza dei generatori già attivi, ad esempio 30% (Idle). Quindi anche se i generatori accesi dovrebbero per rispettare il parametro Gap stare sull’8% di potenza andranno al valore di Idle impostato;
...
l risultato delle impostazioni effettuate è visualizzato nella parte in alto a destra della pagina OpenTherm “Stato Richiesta Generatori”:
PHOTO TBD
Abilita Set/Riscaldamento: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti non sta arrivando nessuna richiesta a OpenTherm.
Abilita Set/Sanitario: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto per la produzione di Acqua calda Sanitaria. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti o dalla pagina ACS non sta arrivando nessuna richiesta a OpenTherm.
Numero Generatori attivi (cascata): indica quanti generatori sono stati attivati per la cascata in riscaldamento (non per la produzione ACS).
l’ultimo rettangolo in basso (riquadro giallo) è il countdown della pausa tra variazioni in centesimi di secondo.
PHOTO TBD
Facendo sempre riferimento all'immagine relativa alla sezione Generatori della pagina OpenTherm:
PHOTO TBD
si fa presente quanto segue:
...
Nella parte inferiore della pagina OpenTherm si riporta per ogni generatore il risultato delle richieste di riscaldamento e ACS (riquadro rosso) e il feedback dai generatori verso il sistema REG (giallo):
PHOTO TBD
Evidenziato in rosso si trova:
...
A parità di priorità l’accensione segue l’ordine numerico dei generatori per la prima accensione, mentre per le successive accensioni i generatori vengono fatti ruotare:
PHOTO TBD
Quindi nell’esempio sopra riportato alla prima accensione l’ordine sarà:
...