Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

OBJECTIVE

...

The following image shows, within the OpenTherm page of the RegConfig, the position of the System Cascade control Algorithm section (red) and the Buffer tank Compensation Temperature section (blue), closely related to the PID cascade algorithm:

PHOTO TBD

The cascade algorithm can be of three types:

...

Enabled OpenTherm generators are those generators that have a number (which can range from 1, highest priority, to 8, lowest priority) in the Generators section (highlighted in green) on the OpenTherm page and not OFF in the box corresponding to the “Heat/Cool” column. The number indicates the priority of the call, so in the image below G1 and G3 generators have priority 1 (they are called first), while G2 has priority 2 and G4 priority 3:

...

Warning

Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.

...

The addition or switching off of a generator must always observe the following 3 parameters:

  • N. Generatori Start : indica il numero di generatori che vengono accessi partendo dalla condizione “tutti i generatori OpenTherm sono spenti”. Ad esempio si ipotizza di porre il numero di generatori Start pari a 2: si è nella condizione “tutti i generatori OpenTherm sono spenti” e l’algoritmo di cascata ha come risultato l’accensione di un solo generatore, però come minimo ne accende 2 contemporaneamente. Dopo l’accensione (e quindi perlomeno dopo il tempo indicato da “Pausa tra variazioni”) l’algoritmo potrà valutare se il numero di generatori è congruo alla richiesta dell’impianto (e quindi lasciarlo invariato), oppure diminuirlo o aumentarlo; il numero di generatori allo start è utile nel caso in cui ci siano impianti con molti generatori. Si supponga di avere un impianto con 8 generatori: se il sistema parte con un solo generatore e poi ogni “Pausa tra variazioni” (tipicamente 3 minuti) ne aggiunge un altro, passeranno almeno 21 minuti prima che il sistema vada a pieno regime; impostando invece il numero iniziale a 4 il sistema parte subito con 4 generatori, e poi si deciderà se aumentare tale numero (e comunque al massimo in 12 minuti andrebbe al massimo) o diminuirlo;

  • N. Generatori Minimo: indica il numero minimo di generatori attivi. Se per esempio è impostato su 3 e attualmente sono attivi 3 generatori, anche se l’algoritmo di cascata determinasse la necessità di spegnere un ulteriore generatore, non ne verrebbe spento nessuno; detto in altro modo non verrebbero mai lasciati accesi meno di 3 generatori (nota bene: si intende che il sistema REG abilita 3 generatori i quali possono poi decidere di spegnere la fiamma/il compressore, perché determinano che la loro temperatura di mandata è soddisfatta);

  • N. Generatori Massimo: indica il numero massimo di generatori che possono essere contemporaneamente accesi. Se sono abilitati 5 generatori, ma il numero massimo è pari a 3 significa che al massimo l’algoritmo può accendere 3 generatori anche se ne servirebbero 4. Questa scelta ha come conseguenza diretta il fatto che il set point potrebbe non essere mai raggiunto o potrebbe essere raggiunto, ma in un arco di tempo molto lungoGenerators: indicates the number of generators that are switched on starting from the condition “all OpenTherm generators are off”. For example, let us assume that the Start generators number is 2: you are in the condition “all OpenTherm generators are off” and the cascade algorithm results in only one generator switched on, but at least two generators are switched on at the same time. After switch-on (and therefore at least after the time indicated by “Stop between changes”) the algorithm may assess if the number of generators is appropriate to the demand of the system (and therefore leave it unchanged) or decrease or increase it; the number of generators at the start is useful if there are systems with many generators. Let us suppose we have a system with 8 generators: if the system starts with only one generator and then every “Stop between changes” (typically 3 minutes) adds another one, it will pass at least 21 minutes before the system goes at full speed; instead, if we set the initial number at 4, the system starts immediately with 4 generators, and then we decide if increase this number (and, in any case, in 12 minutes it would go to the maximum) or decrease it. 

  • N. Minimum Generators: indicates the minimum number of active generators. If, for example, it is set to 3 and 3 generators are currently active, even if the cascade algorithm were to determine the need to switch off a further generator, none would be switched off; in another way, they would have never less than 3 generators on (Note: this means that the REG System enables 3 generators which can then decide to switch off the flame/compressor, because they determine that their water outlet temperature is satisfied).

  • N. Maximum Generators: indicates the maximum number of generators that can be switched on at the same time. If 5 generators are enabled, but the maximum number is 3, this means that the algorithm can switch on maximum 3 generators, even though 4 would be needed. This choice has the direct consequence that the set point may never be reached or that may be reached but over a long period of time.

Una volta definito il numero di generatori start/minimo/massimo è necessario definire i seguenti parametri:

...

l risultato delle impostazioni effettuate è visualizzato nella parte in alto a destra della pagina OpenTherm “Stato Richiesta Generatori”:

PHOTO TBD

  • Abilita Set/Riscaldamento: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti non sta arrivando nessuna richiesta a OpenTherm.

  • Abilita Set/Sanitario: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto per la produzione di Acqua calda Sanitaria. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti o dalla pagina ACS non sta arrivando nessuna richiesta a OpenTherm.

  • Numero Generatori attivi (cascata): indica quanti generatori sono stati attivati per la cascata in riscaldamento (non per la produzione ACS).

  • l’ultimo rettangolo in basso (riquadro giallo) è il countdown della pausa tra variazioni in centesimi di secondo.

PHOTO TBD

Facendo sempre riferimento all'immagine relativa alla sezione Generatori della pagina OpenTherm:

PHOTO TBD

si fa presente quanto segue:

...

Nella parte inferiore della pagina OpenTherm si riporta per ogni generatore il risultato delle richieste di riscaldamento e ACS (riquadro rosso) e il feedback dai generatori verso il sistema REG (giallo):

PHOTO TBD

Evidenziato in rosso si trova:

...

A parità di priorità l’accensione segue l’ordine numerico dei generatori per la prima accensione, mentre per le successive accensioni i generatori vengono fatti ruotare:

PHOTO TBD

Quindi nell’esempio sopra riportato alla prima accensione l’ordine sarà:

...