OBJECTIVE
This technical information details the new PID cascade algorithm that can be selected within the OpenTherm page of the RegConfig Configurator.
...
Enabled OpenTherm generators are those generators that have a number (which can range from 1, highest priority, to 8, lowest priority) in the Generators section (highlighted in green) on the OpenTherm page and not OFF in the box corresponding to the “Heat/Cool” column. The number indicates the priority of the call, so in the image below G1 and G3 generators have priority 1 (they are called first), while G2 has priority 2 and G4 priority 3:
...
Warning
Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.
...
However, it is important to underline that “PID Cascade” and “Buffer Tank Compensation Temperature” are two different and separate functions, which can operate together or separately (e.g., the “Buffer Tank Compensation Temperature” can be also used for other types of cascade algorithms, and also for Parallel functioning), which incidentally “share” the same sensor, as the requirement for both algorithms is to monitor the “final” temperature provided by the group of generators.
Note
The “Buffer Tank Compensation Temperature” is not the subject of this technical part, which instead focuses on the “PID Cascade”.
...
so, if we consider a delta T of 4 K and a delay T of 5 minutes before switching on a second generator, then the value of Pid I to be entered is 87 (1740 / 4 * 5). The lower the Pid I parameter, the more time will pass before an additional generator is added.
Note
The values 160 and 1740 were derived from formulas implemented for this specific algorithm!
...
The demand for H = Heating, W = DHW, and C = Cooling;
The required temperature in heating or cooling [°C];
The power required in heating or cooling [%].
Warning
If the generator is used for DHW production only both the required temperature and power are zero, the values that are passed in case of DHW production are those that are displayed in Generator Demand Status (top right of the OpenTherm page)
...