 OBJECTIVE

...

The following image shows, within the OpenTherm page of the RegConfig, the position of the Heating Cascade Algorithm Control section and the Secondary Heating Temperature Compensation section, closely related to the PID cascade algorithm:

PHOTO TBD

The cascade algorithm can be of three types:

...

Attenzione: non utilizzare G0 in quanto è il generatore OpenTherm utilizzato con il prodotto DOT, non con il sistema REG, quindi nella logica di cascata non viene mai considerato.

Warning

Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.

...

However, it is important to underline that “PID Cascade” and “Buffer Tank Compensation Temperature” are two different and separate functions, which can operate together or separately (e.g., the “Buffer Tank Compensation Temperature” can be also used for other types of cascade algorithms, and also for Parallel functioning), which incidentally “share” the same sensor, as the requirement for both algorithms is to monitor the “final” temperature provided by the group of generators.

Note

The “Buffer Tank Compensation Temperature” is not the subject of this technical part, which instead focuses on the “PID Cascade”.

...

so, if we consider a delta T of 4 K and a delay T of 5 minutes before switching on a second generator, then the value of Pid I to be entered is 87 (1740 / 4 * 5). The lower the Pid I parameter, the more time will pass before an additional generator is added.

Note

The values 160 and 1740 were derived from formulas implemented for this specific algorithm!

...

The lower part of the OpenTherm page shows for each generator the result of the heating/cooling and DHW requests (red box) and the feedback from the generators to the REG System (yellow):

PHOTO TBD

Highlighted in red you have:

...

If the generator is used for DHW production only both the required temperature and power are zero, the values that are passed in case of DHW production are those that are displayed in Generator Demand Status (top right of the OpenTherm page)

La pagina OpenTherm può gestire sia caldaie mediante protocollo OpenTherm (senza firmware dedicato) sia pompe di calore o caldaie mediante protocollo Modbus con firmware dedicato. In giallo si evidenziano i valori trasmessi dalla caldaia o dalla pompa di calore e sono strettamente legati a come il produttore dei generatori ha implementato il protocollo OpenTherm sulla caldaia o il protocollo Modbus sulla pompa di calore/caldaia (fare sempre riferimento alla documentazione del generatore a riguardo o nel caso di firmware dedicati alla documentazione fornita con il firmware). Passando con il mouse sopra i vari rettangoli/quadrati compare un tag con una descrizione estesaThe OpenTherm page can manage both boiler via OpenTherm protocol (without dedicated firmware) and heat pumps or boilers via Modbus protocol with dedicated firmware. In yellow are highlighted the values transmitted by the boiler or the heat pump and are closely linked to how the generators’ manufacturer has implemented the OpenTherm protocol on the boiler or the Modbus protocol on the heat pump/boiler (always refer to the documentation of the generator or, in the case of dedicated firmware, to the documentation supplied with the firmware). By hovering the mouse over the various rectangles/squares, a tag with extended description appears:

  • Stato Generatore: indica in che stato si trova il generatore (G = guasto, R = riscaldamento, SA = Acqua sanitaria, F = fiamma, C = condizionamento, ecc.). Se non implementato nessun quadrativo verrà popolato con le spunte.

  • Temperatura mandata, Temperatura ritorno, Temperatura ACS [°C]: sono le letture dei sensori del generatore se presenti e/o se mappate nel firmware dedicato.

  • Pot.: potenza erogata dal generatore in %, in kW elettrici, in kW termici (fare riferimento al manuale del produttore della caldaia o al manuale del firmware dedicato).

  • Errore OT: errori Opentherm più frequenti (Ra = richiesta assistenza, Rr = reset remoto abilitato, Bp = Bassa pressione acqua, ecc.). Nel caso di firmware dedicato fare riferimento alla documentazione fornita per la decodifica.

  • Errore OEM: indicazione del numero dell’errore, fare riferimento al manuale del generatore per la diagnostica o alla documentazione del firmware dedicato.

  • Reset: reset dell’errore, funziona solo se implementato o se la caldaia lo gestisce, fare riferimento al manuale del generatore per la diagnostica o alla documentazione del firmware dedicato.

...

Si ipotizza di avere selezionato 1 come numero di generatori Start e Minimo, mentre il numero Massimo è 9:

PHOTO TBD

L’impianto in oggetto ha 4 generatori OpenTherm:

...