OBJECTIVE
...
The following image shows, within the OpenTherm page of the RegConfig, the position of the Heating Cascade Algorithm Control section and the Secondary Heating Temperature Compensation section, closely related to the PID cascade algorithm:
PHOTO TBD
The cascade algorithm can be of three types:
...
Attenzione: non utilizzare G0 in quanto è il generatore OpenTherm utilizzato con il prodotto DOT, non con il sistema REG, quindi nella logica di cascata non viene mai considerato.
Warning
Do not use G0 as it is the OpenTherm generator used with the DOT product, not with the REG system, therefore it is never considerate in the cascade logic.
...
However, it is important to underline that “PID Cascade” and “Buffer Tank Compensation Temperature” are two different and separate functions, which can operate together or separately (e.g., the “Buffer Tank Compensation Temperature” can be also used for other types of cascade algorithms, and also for Parallel functioning), which incidentally “share” the same sensor, as the requirement for both algorithms is to monitor the “final” temperature provided by the group of generators.
Note
The “Buffer Tank Compensation Temperature” is not the subject of this technical part, which instead focuses on the “PID Cascade”.
...
so, if we consider a delta T of 4 K and a delay T of 5 minutes before switching on a second generator, then the value of Pid I to be entered is 87 (1740 / 4 * 5). The lower the Pid I parameter, the more time will pass before an additional generator is added.
Note
The values 160 and 1740 were derived from formulas implemented for this specific algorithm!
N. Start Generators: indicates the number of generators that are switched on starting from the condition “all OpenTherm generators are off”. For example, let us assume that the Start generators number is 2: you are in the condition “all OpenTherm generators are off” and the cascade algorithm results in only one generator switched on, but at least two generators are switched on at the same time. After switch-on (and therefore at least after the time indicated by “Stop between changes”) the algorithm may assess if the number of generators is appropriate to the demand of the system (and therefore leave it unchanged) or decrease or increase it; the number of generators at the start is useful if there are systems with many generators. Let us suppose we have a system with 8 generators: if the system starts with only one generator and then every “Stop between changes” (typically 3 minutes) adds another one, it will pass at least 21 minutes before the system goes at full speed; instead, if we set the initial number at 4, the system starts immediately with 4 generators, and then we decide if increase this number (and, in any case, in 12 minutes it would go to the maximum) or decrease it.
N. Minimum Generators: indicates the minimum number of active generators. If, for example, it is set to 3 and 3 generators are currently active, even if the cascade algorithm were to determine the need to switch off a further generator, none would be switched off; in another way, they would have never left on less than 3 generators (Note: this means that the REG System enables 3 generators which can then decide to switch off the flame/compressor, because they determine that their water outlet temperature is satisfied).
N. Maximum Generators: indicates the maximum number of generators that can be switched on at the same time. If 5 generators are enabled, but the maximum number is 3, this means that the algorithm can switch on maximum 3 generators, even though 4 would be needed. This choice has the direct consequence that the set point may never be reached or that may be reached but over a long period of time.
I parametri Power e Temperatura degradata fanno riferimento all'algoritmo di controllo Cascata di Potenza, quindi i valori inseriti vengono ignorati in caso si selezioni l’algoritmo di controllo PI di Cascata.
Il risultato delle impostazioni effettuate è visualizzato nella parte in alto a destra della pagina OpenTherm “Stato Richiesta Generatori”The Power and Degraded Temperature parameters refer to the Power Cascade, so the values entered are ignored if the Cascade PI control algorithm is selected.
The result of the settings made is displayed at the top right of the OpenTherm page “Generator Demand Status”:
PHOTO TBD
Abilita Set/Riscaldamento: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto. Per le pompe di calore il set point è di riscaldamento o di raffrescamento. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti non sta arrivando nessuna richiesta a OpenTherm.
Abilita Set/Sanitario: se il quadrato ha la spunta significa che c'è una richiesta ai generatori e nel rettangolo a destra è indicato il set point richiesto per la produzione di Acqua calda Sanitaria. Se il quadrato non è spuntato e il set point è a zero significa che dai circuiti o dalla pagina ACS non sta arrivando nessuna richiesta a OpenTherm.
Numero Generatori attivi (cascata): indica quanti generatori sono stati attivati per la cascata in riscaldamento o in raffrescamento (non per la produzione ACS).
l’ultimo rettangolo in basso (riquadro giallo) è il countdown della pausa tra variazioni in centesimi di secondo.
PHOTO TBD
Facendo sempre riferimento all'immagine relativa alla sezione Generatori della pagina OpenTherm:
PHOTO TBD
si fa presente quanto segue:
...
Nella parte inferiore della pagina OpenTherm si riporta per ogni generatore il risultato delle richieste di riscaldamento/raffrescamento e ACS (riquadro rosso) e il feedback dai generatori verso il sistema REG (giallo):
PHOTO TBD
Evidenziato in rosso si trova:
...
Si ipotizza di avere selezionato 1 come numero di generatori Start e Minimo, mentre il numero Massimo è 9:
PHOTO TBD
L’impianto in oggetto ha 4 generatori OpenTherm:
...